Inspections for the day of: Wednesday, January 21, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02486 BLD-Aging Inspection1/21/20091/21/20091/26/2009 3:12:13 PMPDONE
Pending project related fire alarm permit site inspection.
FIR08-00797 INSP-Sprinkler Rough-in1/21/20091/21/20091/21/2009 4:51:22 PMPPART
OH modifications are approved for cover as annotated and initialed with today's date on the approved plans, note two pendent heads at the common corridor to be replaced with matching response and type, mail room not yet finished.
BLD08-02301 FIRE-Final Inspection1/21/20091/21/20091/21/2009 4:48:35 PMPPASS
C/N items completed, life safety finaled.
FIR08-00812 INSP-Final Inspection1/21/20091/21/20091/21/2009 4:47:46 PMPPASS
Fire sprinkler permit finaled.
FIR08-00737 INSP-Sprinkler Rough-in/Hydro1/21/20091/21/20091/21/2009 12:45:02 PMAPART
New 2" steel pipe and branchline outlets above the sheetrock ceiling at the UPS room are okay for cover.
FIR09-00004 INSP-Final Inspection1/20/20091/21/20091/21/2009 12:43:05 PMAPASS
Fire alarm field testing passed, permit finaled.
FIR08-00812 INSP-Final Inspection1/21/20091/21/20091/21/2009 12:42:19 PMAPASS
Correction verified for completion, inspection passed.