FIR08-00626
| INSP-Sprinkler Rough-in/Hydro | 1/21/2009 | 1/21/2009 | 1/22/2009 1:16:17 PM | P | PART |
|
|
UG supply hydro failed. UG fdc hydro passed.
|
FIR08-00672
| FIR-Aging Inspection | 1/21/2009 | 1/21/2009 | 1/22/2009 8:20:12 AM | | NR |
|
|
Work is in progress
|
FIR07-01031
| INSP-Sprinkler Rough-in | 1/20/2009 | 1/21/2009 | 1/22/2009 8:00:14 AM | P | PASS |
|
|
See the as-builts with the date of 1-21-2009 for the location where the sprinkler piping is ok to cover
|
FIR07-01032
| INSP-Sprinkler Rough-in | 1/20/2009 | 1/21/2009 | 1/22/2009 7:59:30 AM | A | PASS |
|
|
See the as-builts with the date of 1-21-2009 for the location where the sprinkler piping is ok to cover
|
FIR08-00593
| INSP-Alarm Testing | 1/20/2009 | 1/21/2009 | 1/21/2009 3:33:00 PM | P | FAIL |
|
|
The manual pull station is mounted too high. The tamper switch for the PIV had to be adjusted while on site. All other items tested ok.
|
FIR08-00593
| INSP-Sprinkler Rough-in | 1/20/2009 | 1/21/2009 | 1/21/2009 3:32:24 PM | P | FAIL |
|
|
The manual pull station is mounted too high. The tamper switch for the PIV had to be adjusted while on site. All other items tested ok.
|
FIR08-00541
| INSP-Final Inspection | 1/21/2009 | 1/21/2009 | 1/21/2009 3:28:09 PM | P | FAIL |
|
|
The forward flush passed. Bruce needs to change the mixed temperature pendants to be all 155 degree except in locations as required
|
FIR08-00434
| INSP-Final Inspection | 1/21/2009 | 1/21/2009 | 1/21/2009 3:19:23 PM | P | PASS |
|
|
Permit finaled
|
FIR08-00771
| INSP-Final Inspection | 1/21/2009 | 1/21/2009 | 1/21/2009 3:14:05 PM | P | FAIL |
|
|
The interconnection between the new NAC panel and the existing FACP passed. What failed is that many of the new audio/visual devices are mounted too low. Two 110 cd strobes in the large open area on the north side of the building are mounted almost against building columns so they need to be relocated over so as to be unobstructed. A corridor on the south side has no notification installed and a device will need to be added. When this is done the system will need to be inspected.
|
FIR08-00785
| INSP-Final Inspection | 1/21/2009 | 1/21/2009 | 1/21/2009 3:10:48 PM | P | FAIL |
|
|
The approved fire sprinkler plans show many rooms where the modified sprinkler pendants are to be changed to a quick responce type. The sprinkler heads installed are of the standard responce type.
|
BLD08-02067
| FIRE-Final Inspection | 1/21/2009 | 1/21/2009 | 1/21/2009 3:09:26 PM | P | FAIL |
|
|
The life safety can be passed when the project related fire alarm and fire sprinkler permits are finaled
|
FIR08-00760
| INSP-Sprinkler Rough-in/Hydro | 1/20/2009 | 1/21/2009 | 1/21/2009 1:20:00 PM | A | PART |
|
|
The sprinkler piping is ok to cover on both floors except for the first floor west entertainment room. The heads in this room are overspaced.
|