Inspections for the day of: Wednesday, January 21, 2009.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00626 INSP-Sprinkler Rough-in/Hydro1/21/20091/21/20091/22/2009 1:16:17 PMPPART
UG supply hydro failed. UG fdc hydro passed.
FIR08-00672 FIR-Aging Inspection1/21/20091/21/20091/22/2009 8:20:12 AM NR
Work is in progress
FIR07-01031 INSP-Sprinkler Rough-in1/20/20091/21/20091/22/2009 8:00:14 AMPPASS
See the as-builts with the date of 1-21-2009 for the location where the sprinkler piping is ok to cover
FIR07-01032 INSP-Sprinkler Rough-in1/20/20091/21/20091/22/2009 7:59:30 AMAPASS
See the as-builts with the date of 1-21-2009 for the location where the sprinkler piping is ok to cover
FIR08-00593 INSP-Alarm Testing1/20/20091/21/20091/21/2009 3:33:00 PMPFAIL
The manual pull station is mounted too high. The tamper switch for the PIV had to be adjusted while on site. All other items tested ok.
FIR08-00593 INSP-Sprinkler Rough-in1/20/20091/21/20091/21/2009 3:32:24 PMPFAIL
The manual pull station is mounted too high. The tamper switch for the PIV had to be adjusted while on site. All other items tested ok.
FIR08-00541 INSP-Final Inspection1/21/20091/21/20091/21/2009 3:28:09 PMPFAIL
The forward flush passed. Bruce needs to change the mixed temperature pendants to be all 155 degree except in locations as required
FIR08-00434 INSP-Final Inspection1/21/20091/21/20091/21/2009 3:19:23 PMPPASS
Permit finaled
FIR08-00771 INSP-Final Inspection1/21/20091/21/20091/21/2009 3:14:05 PMPFAIL
The interconnection between the new NAC panel and the existing FACP passed. What failed is that many of the new audio/visual devices are mounted too low. Two 110 cd strobes in the large open area on the north side of the building are mounted almost against building columns so they need to be relocated over so as to be unobstructed. A corridor on the south side has no notification installed and a device will need to be added. When this is done the system will need to be inspected.
FIR08-00785 INSP-Final Inspection1/21/20091/21/20091/21/2009 3:10:48 PMPFAIL
The approved fire sprinkler plans show many rooms where the modified sprinkler pendants are to be changed to a quick responce type. The sprinkler heads installed are of the standard responce type.
BLD08-02067 FIRE-Final Inspection1/21/20091/21/20091/21/2009 3:09:26 PMPFAIL
The life safety can be passed when the project related fire alarm and fire sprinkler permits are finaled
FIR08-00760 INSP-Sprinkler Rough-in/Hydro1/20/20091/21/20091/21/2009 1:20:00 PMAPART
The sprinkler piping is ok to cover on both floors except for the first floor west entertainment room. The heads in this room are overspaced.