ELE10-00565
| ELE-Aging Inspection | 1/21/2014 | 1/21/2014 | 1/22/2014 3:47:00 PM | | DONE |
|
|
Drove by still under construction
|
ELE14-00155
| Temporary Service | 1/20/2014 | 1/21/2014 | 1/21/2014 4:45:00 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00151
| Temporary Service | 1/20/2014 | 1/21/2014 | 1/21/2014 4:29:50 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00154
| Temporary Service | 1/20/2014 | 1/21/2014 | 1/21/2014 4:17:55 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00153
| Temporary Service | 1/20/2014 | 1/21/2014 | 1/21/2014 4:09:57 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00125
| Electrical Rough-In | 1/21/2014 | 1/21/2014 | 1/21/2014 3:57:59 PM | P | PASS |
|
|
cover for walls Phone #: ###-#### >> Inspection requested via web by Stan Woodward Wall rough in ok cover
|
ELE13-01291
| Conference | 1/21/2014 | 1/21/2014 | 1/21/2014 3:41:29 PM | P | DONE |
|
|
Contract Tony Keen at ###-####. Phone #: ###-#### >> Inspection requested via web by Tina Payne Discussed conduits and boxes installed in precast parking barriers. Contractor to verify 3rd party listing on company making barriers. APA Certified company listed on spec sheet for barriers
|
ELE13-03031
| Electrical Rough-In | 1/21/2014 | 1/21/2014 | 1/21/2014 3:14:33 PM | P | PASS |
|
|
Contact Wes Powell - ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Corridor ceiling rough in ok cover
|
ELE14-00022
| Electrical Rough-In | 1/20/2014 | 1/21/2014 | 1/21/2014 2:33:55 PM | A | PASS |
|
|
Call to get access through front door. Phone #: ###-#### >> Inspection requested via web by robert feller Walls and bathroom lids rough in ok cover
|
ELE13-03295
| Final | 1/17/2014 | 1/21/2014 | 1/21/2014 2:26:05 PM | A | PASS |
|
|
Contact: Justin Hugo... Please call half hour before going so Justin can meet you there Phone #: ###-#### >> Inspection requested via web by Deb Gooden No card posted. Final ok
|
ELE13-03399
| Electrical Rough-In | 1/17/2014 | 1/21/2014 | 1/21/2014 2:09:00 PM | A | PASS |
|
|
Contact: Frank Yantis Phone #: ###-#### >> Inspection requested via web by Deb Gooden Soffit and TV wall rough in ok cover
|
ELE13-02977
| Final | 1/20/2014 | 1/21/2014 | 1/21/2014 1:18:17 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Girard Final ok
|
ELE14-00139
| Rough-In Permanent Service | 1/20/2014 | 1/21/2014 | 1/21/2014 1:01:24 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Rough in ok cover p/s u/g n ok
|
ELE13-03094
| Final | 1/21/2014 | 1/21/2014 | 1/21/2014 12:42:31 PM | A | PASS |
|
|
code 4224 Phone #: ###-#### >> Inspection requested via web by Bob Glenn Final ok
|
ELE13-03458
| Final | 1/17/2014 | 1/21/2014 | 1/21/2014 10:46:34 AM | A | FAIL |
|
|
call steve with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig Receptical outlet located in kitchenette not working, unable to test. Receptical located in closet near west reception area not covered.
|
ELE13-03049
| Final | 1/20/2014 | 1/21/2014 | 1/21/2014 10:23:36 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Buster Bowen Final ok
|
ELE13-02755
| Final | 1/20/2014 | 1/21/2014 | 1/21/2014 9:53:30 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Chesnut 440.4- Over currect protective device shall be sized to nameplate rating , 25 amp max. 210.52- A receptical outlet shall be located at end of peninsula counter top. 310.12(C)- Conductors used as ungrounded conductors shall be clearly distinguishable from grounded conductors.
|
ELE13-02034
| Final | 1/20/2014 | 1/21/2014 | 1/21/2014 9:42:08 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Chesnut 440.4(C)- Overcurrent protective device shall be sized to nameplate rating, 20 amp max. 310.12(C)- Conductors used as ungrounded conductors shall be clearly distinguishable from grounded conductors.
|
ELE14-00152
| Rough-In Permanent Service | 1/20/2014 | 1/21/2014 | 1/21/2014 8:58:32 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
GCE13-00181
| GCE-Rough-In Permanent Service | 1/17/2014 | 1/21/2014 | 1/21/2014 8:37:37 AM | A | PASS |
|
|
(Mandatory Inspection)Mark ###-#### Service rough in ok p/s u/g n ok
|