ELE10-01793
| ELE-Aging Inspection | 1/21/2014 | 1/21/2014 | 1/24/2014 6:25:18 AM | | CANC |
|
|
|
ELE10-00628
| ELE-Aging Inspection | 1/21/2014 | 1/21/2014 | 1/24/2014 6:24:56 AM | | CANC |
|
|
|
ELE14-00097
| Electrical Rough-In | 1/21/2014 | 1/21/2014 | 1/21/2014 2:59:08 PM | P | PASS |
|
|
rough-in for tenant improvement. Service is not effected by tenant improvement Phone #: ###-#### >> Inspection requested via web by David Mackey walls and hard lid ok cover
|
ELE13-03481
| Final | 1/20/2014 | 1/21/2014 | 1/21/2014 2:42:42 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Kendra Lanham called, shall label breakers at service and check riser strap
|
ELE13-03444
| Final | 1/21/2014 | 1/21/2014 | 1/21/2014 1:49:18 PM | P | PASS |
|
|
Mark Gibson is contact at ###-####, thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis ok final
|
ELE14-00150
| Electrical Rough-In | 1/20/2014 | 1/21/2014 | 1/21/2014 1:23:05 PM | P | PART |
|
|
wall rough in ready call dave with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig called, part walls ok cover, except around panel area, strappng, foreign piping to be cleaned up
|
ELE13-03084
| Final | 1/21/2014 | 1/21/2014 | 1/21/2014 1:01:03 PM | P | PASS |
|
|
Garage door entrance code 1979E. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
|
ELE14-00174
| Temporary Service | 1/21/2014 | 1/21/2014 | 1/21/2014 12:20:33 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00103
| Electrical Rough-In | 1/20/2014 | 1/21/2014 | 1/21/2014 12:15:33 PM | A | PASS |
|
|
Contact Ben if any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Ben Archibald ri ok
|
ELE14-00103
| Permanent Service | 1/21/2014 | 1/21/2014 | 1/21/2014 12:12:05 PM | P | PASS |
|
|
Contact Ben if any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Ben Archibald p/s u/g n ok
|
ELE13-02082
| Final | 1/18/2014 | 1/21/2014 | 1/21/2014 10:25:03 AM | A | PASS |
|
|
please Final, this was completed by another contractor under permit #ELE14-00065 Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack ok final
|
ELE14-00087
| Electrical Rough-In | 1/20/2014 | 1/21/2014 | 1/21/2014 10:16:03 AM | A | PASS |
|
|
Please call Meredith ###-#### when you are on your way. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ri ok
|
ELE14-00095
| Electrical Rough-In | 1/17/2014 | 1/21/2014 | 1/21/2014 9:49:49 AM | A | FAIL |
|
|
I have the ceiling ready for a cover inspection thanks Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk called, left correction notice, NEC 362.30(A) shall support ent within 3' of box, 330.30(B) shall support mc within 12" of box, 300.11(A)(B) grid shall not support raceway, raceways shall nor support other raceways, 314.23 shall securely support box in ceiling, 725.25 shall remove abandoned lv cables, BCC no violations shall be retained
|
ELE13-02840
| Final | 1/20/2014 | 1/21/2014 | 1/21/2014 9:26:31 AM | A | PASS |
|
|
If locked, call me for key location. Thanks Bob!! Phone #: ###-#### >> Inspection requested via web by Julie Schroder ok final
|
ELE14-00161
| Rough-In Permanent Service | 1/20/2014 | 1/21/2014 | 1/21/2014 8:50:21 AM | A | FAIL |
|
|
Key for door is located inside far right chain link gate (combo 7208, once inside right hand door will be unlocked,key is hanging on fence to left Phone #: ###-#### >> Inspection requested via web by ben wolf called, told to identify breaker, move generator to get min 42" clearance off wall
|
ELE14-00021
| Electrical Rough-In | 1/17/2014 | 1/21/2014 | 1/21/2014 8:28:29 AM | A | PART |
|
|
Thank you! Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld partial walls and ceiling ok cover, left correction notice NEC 210.62 shall provide show room receptacles each 12' or fraction thereof
|
ELE14-00087
| Rough-In Permanent Service | 1/17/2014 | 1/21/2014 | 1/20/2014 12:45:00 PM | A | CANC |
|
|
Please call homeowner Meredith when on your way ###-####. Thank You Phone #: ###-#### >> Inspection requested via web by Clay Morgan Inspection cancelled from web by: Clay Morgan
|