Inspections for the day of: Tuesday, January 21, 2014.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01793 ELE-Aging Inspection1/21/20141/21/20141/24/2014 6:25:18 AM CANC
ELE10-00628 ELE-Aging Inspection1/21/20141/21/20141/24/2014 6:24:56 AM CANC
ELE14-00097 Electrical Rough-In1/21/20141/21/20141/21/2014 2:59:08 PMPPASS
rough-in for tenant improvement. Service is not effected by tenant improvement Phone #: ###-#### >> Inspection requested via web by David Mackey walls and hard lid ok cover
ELE13-03481 Final1/20/20141/21/20141/21/2014 2:42:42 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Kendra Lanham called, shall label breakers at service and check riser strap
ELE13-03444 Final1/21/20141/21/20141/21/2014 1:49:18 PMPPASS
Mark Gibson is contact at ###-####, thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis ok final
ELE14-00150 Electrical Rough-In1/20/20141/21/20141/21/2014 1:23:05 PMPPART
wall rough in ready call dave with questions thanks
Phone #: ###-#### >> Inspection requested via web by Don Lustig called, part walls ok cover, except around panel area, strappng, foreign piping to be cleaned up
ELE13-03084 Final1/21/20141/21/20141/21/2014 1:01:03 PMPPASS
Garage door entrance code 1979E. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
ELE14-00174 Temporary Service1/21/20141/21/20141/21/2014 12:20:33 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE14-00103 Electrical Rough-In1/20/20141/21/20141/21/2014 12:15:33 PMAPASS
Contact Ben if any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Ben Archibald ri ok
ELE14-00103 Permanent Service1/21/20141/21/20141/21/2014 12:12:05 PMPPASS
Contact Ben if any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Ben Archibald p/s u/g n ok
ELE13-02082 Final1/18/20141/21/20141/21/2014 10:25:03 AMAPASS
please Final, this was completed by another contractor under permit #ELE14-00065 Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack ok final
ELE14-00087 Electrical Rough-In1/20/20141/21/20141/21/2014 10:16:03 AMAPASS
Please call Meredith ###-#### when you are on your way. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ri ok
ELE14-00095 Electrical Rough-In1/17/20141/21/20141/21/2014 9:49:49 AMAFAIL
I have the ceiling ready for a cover inspection thanks Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk called, left correction notice, NEC 362.30(A) shall support ent within 3' of box, 330.30(B) shall support mc within 12" of box, 300.11(A)(B) grid shall not support raceway, raceways shall nor support other raceways, 314.23 shall securely support box in ceiling, 725.25 shall remove abandoned lv cables, BCC no violations shall be retained
ELE13-02840 Final1/20/20141/21/20141/21/2014 9:26:31 AMAPASS
If locked, call me for key location. Thanks Bob!! Phone #: ###-#### >> Inspection requested via web by Julie Schroder ok final
ELE14-00161 Rough-In Permanent Service1/20/20141/21/20141/21/2014 8:50:21 AMAFAIL
Key for door is located inside far right chain link gate (combo 7208, once inside right hand door will be unlocked,key is hanging on fence to left Phone #: ###-#### >> Inspection requested via web by ben wolf called, told to identify breaker, move generator to get min 42" clearance off wall
ELE14-00021 Electrical Rough-In1/17/20141/21/20141/21/2014 8:28:29 AMAPART
Thank you! Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld partial walls and ceiling ok cover, left correction notice NEC 210.62 shall provide show room receptacles each 12' or fraction thereof
ELE14-00087 Rough-In Permanent Service1/17/20141/21/20141/20/2014 12:45:00 PMACANC
Please call homeowner Meredith when on your way ###-####. Thank You Phone #: ###-#### >> Inspection requested via web by Clay Morgan Inspection cancelled from web by: Clay Morgan