Inspections for the day of: Tuesday, January 21, 2014.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00870 FIRE-Conference1/15/20141/15/2014 P 
Could you check this out and see if it is resolved so we can close permit?
FIR12-00083 FIR-Aging Inspection1/21/20141/21/20141/24/2014 10:03:36 AM NR
I sent an email to steve with simplex requesting a follow up
FIR14-00046 INSP-Sprinkler Rough-in1/21/20141/21/20141/21/2014 3:43:30 PMPPASS
See the city approved plans for location where piping can be covered. This area is next to Anderson Construction office and was three pendant heads.
FIR13-00308 INSP-Sprinkler Rough-in1/17/20141/21/20141/21/2014 3:28:59 PMPPASS
Todays inspection was for the pendant heads installed in the suspended "clouds". Installation and spacing appeared ok.
FIR13-00709 INSP-Sprinkler Rough-in1/17/20141/21/20141/21/2014 3:24:52 PMAPASS
Piping is ok to cover. Two locations of tenting repaired while I waited.
FIR13-00706 INSP-Sprinkler Rough-in1/20/20141/21/20141/21/2014 2:58:24 PMAPASS
Piping in the two restrooms and the area immediately outside of these rooms is ok to cover. There is wood in the soffit above the service counter, which tim frost is ok with. There is wood above the ceiling in the kitchen area that tim is not ok with except for the walls around the office. All of the exposed wood, except at the office will need to cut away, as per agreement with building contractor. Office walls ok due to the addition of one upright sprinker, at deck, in the office.
FIR14-00036 INSP-Sprinkler Rough-in1/17/20141/21/20141/21/2014 2:11:20 PMAPASS
Piping in the seating area is ok to cover.
FIR13-00722 INSP-Final Inspection1/17/20141/21/20141/21/2014 1:21:00 PMAPASS
Permit finaled
BLD13-01675 FIRE-Final Inspection1/21/20141/21/20141/21/2014 1:20:19 PMPPART
A temporary occupancy is being given with scott arellano's permission until the door mag/hardware hase been installed and tested. All other life safety items are ok.
FIR13-00671 INSP-Final Inspection1/17/20141/21/20141/21/2014 1:18:31 PMAPART
This inspection is for temporary occupancy permit request for GC. All FA work completed except for front door mag release. There is no hardware on front door. ok for temp permit, per Scott Aranello on 1/16/14.

-Submitted by Scott Ramella ###-#### cell Phone #: ###-#### >> Inspection requested via web by Scott Ramella
FIR13-00681 INSP-Final Inspection1/16/20141/21/20141/21/2014 11:17:35 AMAPASS
permit finaled
FIR13-00569 INSP-Final Inspection1/20/20141/21/20141/21/2014 11:14:12 AMAPASS
Permit finaled