Inspections for the day of: Tuesday, January 21, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00146 Conference1/17/20141/21/20141/21/2014 5:27:21 PMPDONE
Mike Phone #: ###-#### Talked with homeowner about garage and game room addition. Discussed electrical requirements for exsisting hot tub.
ELE13-03387 Electrical Rough-In1/20/20141/21/20141/21/2014 3:35:47 PMAFAIL
Toby. Ceiling cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy NEC 800.25 Cables shall be supported off ceiling grid. Abandoned cable shall be removed. Cables for future use shall be tagged and indentified.
ELE14-00143 Final1/17/20141/21/20141/21/2014 2:42:48 PMAPASS
robert Phone #: ###-#### final ok
ELE13-02933 Final1/16/20141/21/20141/21/2014 2:24:57 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Bryan Atkins Replaced like for like flood fixture on sign, final ok
ELE14-00167 Electrical Rough-In1/21/20141/21/20141/21/2014 2:20:01 PMPPASS
Dan-Please call prior to insepction Phone #: ###-#### rough-in ok cover walls
ELE13-02604 Final1/17/20141/21/20141/21/2014 1:38:14 PMANH
Contact is Justin Metcalf. Please call when you are headed to the project for this final inspection. Thank you so much and have a great day! Phone #: ###-#### >> Inspection requested via web by Laura Longshaw NO access
ELE13-02890 Final1/21/20141/21/20141/21/2014 1:24:50 PMAPASS
Electrical Final Phone #: ###-#### >> Inspection requested via web by Clay Jackson final ok
ELE14-00148 Electrical Rough-In1/20/20141/21/20141/21/2014 12:47:09 PMAPASS
Electrical rough in 3 dedicated printer circus installed in wall 2 up in the ceiling ready to be dropped into the point of sales and one outlet in newly framed wall that''s waiting for sheetrock. call Mickey Johnson at ###-####9 to unlock door he has several stores down at the UPS Store Phone #: ###-#### >> Inspection requested via web by shane miller rough-in ok cover wall
ELE14-00089 Rough-In Permanent Service1/19/20141/21/20141/21/2014 12:29:10 PMAFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 320.23 Guard strip in attic, shall also be nailed inplace. NEC 312.5(C) Where cables are used, each cable shall be secured to the cabnet NEC 334.30 NM cable shall be sercured within 12 in. of every outlet box, junction box, cabnet
ELE12-01444 Final1/17/20141/21/20141/21/2014 10:12:15 AMAFAIL
Cathy Fangerow (homeowner) Phone #: ###-#### Upstairs master bathroom Exsisting luminaire over shower stall missing cover. NEC 410.10(A) All luminaires installed in wet locations shall be listed and marked suitable for wet locations and shall have GFCI protection
ELE13-03490 Final1/18/20141/21/20141/21/2014 9:38:44 AMAPASS
lock box code is 1359 Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack final ok
ELE13-03490 Electrical Rough-In1/18/20141/21/20141/21/2014 9:37:42 AMAPASS
grid ceiling, lock box code is 1359 Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack rough-in ok cover ceiling grid
ELE13-03351 Electrical Rough-In1/20/20141/21/20141/21/2014 9:27:31 AMAPASS
Please call when on way ###-####. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan rough-in ok cover dettached shop
ELE14-00145 Electrical Rough-In1/17/20141/21/20141/21/2014 8:39:19 AMAPASS
inspection of new room in basement please call Vance @ ###-#### for access Phone #: ###-#### >> Inspection requested via web by Andy Rose rough-in ok cover
ELE14-00135 Temporary Service1/17/20141/21/20141/21/2014 8:15:00 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Heath Thomas t/s u/g n ok
ELE14-00134 Temporary Service1/17/20141/21/20141/21/2014 8:11:56 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Heath Thomas t/s u/g n ok