Inspections for the day of: Wednesday, January 21, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03223 Final1/21/20151/21/20151/21/2015 2:29:30 PMPPASS
For access please call Tom 1/2 hr prior to inspection. ###-####. Inspection requested via web by Terry Scott
Final OK
ELE13-00545 ELE-Aging Inspection1/21/20151/21/20151/21/2015 2:12:13 PM DONE
Contractor to research project and call for final inspection.
ELE15-00138 Rough-In Permanent Service1/20/20151/21/20151/21/2015 2:11:30 PMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI
RI OK , PS, UG, N, OK
ELE14-00299 Final1/21/20151/21/20151/21/2015 1:29:44 PMPCANC
please call ahead 10 min - Stephen Phone #: ###-####
wrong inspection type, needed RI
ELE14-00299 Electrical Rough-In1/21/20151/21/20151/21/2015 1:29:16 PMPPASS
please call ahead 10 min - Stephen Phone #: ###-####
Moving laundry room, ran new home run to washer/dryer location, will be abandoning existing locations.
RI OK to cover, new laundry location
ELE14-03163 Electrical Rough-In1/21/20151/21/20151/21/2015 1:13:52 PMPPASS
Keith Phone #: ###-####
RI OK, upstairs cut in and rewired, basement was all open and wired
ELE14-02803 Final1/21/20151/21/20151/21/2015 12:30:23 PMPPASS
corrections made, Final OK
ELE14-02346 Final1/21/20151/21/20151/21/2015 12:18:06 PMPNR
Ben Phone #: ###-####
inspect for house, hot tub has no electrical permit
different electrical contractor
Violation, work being done, no final allowed per Daryl DeGrange
ELE14-03339 Final1/19/20151/21/20151/21/2015 12:13:52 PMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
FInal OK
ELE13-00018 ELE-Aging Inspection1/21/20151/21/20151/21/2015 10:27:21 AM CANC
Posted correction notice on front door, 1-21-15 10:30 am
ELE14-02847 Final1/20/20151/21/20151/21/2015 9:54:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Eric Schroeder
FInal ok
ELE15-00064 Final1/20/20151/21/20151/21/2015 9:30:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Kelly Felin
corrections made, Final OK
ELE09-02323 ELE-Aging Inspection1/21/20151/21/20151/21/2015 9:25:46 AM DONE
Checked home, still under construction
ELE14-02803 Final1/20/20151/21/20151/21/2015 9:20:10 AMAFAIL
Final inspection please Contact name is Travis Funk Thank you Phone #: ###-#### Inspection requested via web by Deb Gooden
210.8 GFI protection required all kitchen countertops receptacle
408.4 circuit identification required
334.12 B.4 NM not permitted wet or damp locations
330.12 MC cable not permitted wet or damp location without corrosive resistant jacktet
356.30 LFNC shall be secured within 12 inches of boxes.
left message on number provided
ELE14-02232 Final1/20/20151/21/20151/21/2015 8:45:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Don Conley
Final OK