ELE13-00842
| ELE-Aging Inspection | 1/21/2016 | 1/21/2016 | 1/22/2016 11:29:57 AM | | PASS |
|
|
No other permit exists. No inspection history. Waiting on contractor
|
ELE13-01956
| ELE-Aging Inspection | 1/21/2016 | 1/21/2016 | 1/22/2016 11:28:20 AM | | PASS |
|
|
Work completed under ELE13-02014. Expired
|
ELE15-03396
| Electrical Rough-In | 1/21/2016 | 1/21/2016 | 1/21/2016 3:03:06 PM | P | PASS |
|
|
We need an underground inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker East electrical room underground rough in ok cover
|
ELE15-03984
| Electrical Rough-In | 1/20/2016 | 1/21/2016 | 1/21/2016 2:25:14 PM | P | PASS |
|
|
We are requesting a ceiling rough-in inspection for tomorrow 1/21/16 in the afternoon. Our contact is Rich @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Grid 2nd floor rough in ok cover
|
ELE15-03984
| Conference | 1/21/2016 | 1/21/2016 | 1/21/2016 2:24:26 PM | P | DONE |
|
|
Our contact is Rich @ ###-####. Thank you, Phone #: ###-#### NEC 110.26(C)(2)-No clearance required on south side of new equipment due to no accessible panels on south side
|
ELE16-00030
| Final | 1/20/2016 | 1/21/2016 | 1/21/2016 11:16:01 AM | A | PASS |
|
|
James is the site contact Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
ELE16-00017
| Final | 1/20/2016 | 1/21/2016 | 1/21/2016 10:42:00 AM | A | FAIL |
|
|
Bob Phone #: ###-#### 210.8- Receptacle outlet serving island counter space shall have GFCI protection. 406.12- All receptacle outlets installed in dwelling unit shall be tamper resistant type. Island receptacle.
|
ELE16-00198
| Conference | 1/20/2016 | 1/21/2016 | 1/21/2016 10:07:51 AM | A | DONE |
|
|
Juanita Phone #: ###-#### Discussed owner has been general contractor from California in past. Required dedicated garage receptacle circuit, bathroom circuit, 200 amp service, and state law requires owner and or immediate family to do work.
|
ELE16-00055
| Final | 1/20/2016 | 1/21/2016 | 1/21/2016 9:13:47 AM | A | PASS |
|
|
Call George Before hand Phone #: ###-#### Inspection requested via web by Shannon Wall Final ok
|