Inspections for the day of: Wednesday, January 22, 2003.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-00728 ELE-Aging Inspection1/22/20031/22/20031/22/2003 12:00:00 AM PART
alled contractor will check out job and call for inspection 1/23/2003 11:01:39 AM
ELE02-00764 ELE-Aging Inspection1/22/20031/22/20031/22/2003 12:00:00 AM PART
called Mike will set up inspection 1/23/2003 10:38:10 AM
ELE02-03673 Final1/21/20031/22/20031/22/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 01/21/2003 at 11:05:09. Contact: ###-####. ok 1/22/2003 10:13:30 AM
ELE03-00157 Final1/21/20031/22/20031/22/2003 12:00:00 AMANH
###-####

no access notice posted called 1/22/2003 8:34:38 AM
ELE02-02827 Final1/21/20031/22/20031/22/2003 12:00:00 AMAFAIL
FN DAVID- ###-#### cor. posted call 210.52 (C) (5) exception needs outlet too serve left side of sink (island) note both new, and existing outlets shall not extend more than 6 inches back from countertop edge 1/22/2003 9:14:23 AM
ELE02-03818 Electrical Rough-In1/21/20031/22/20031/22/2003 12:00:00 AMAPASS
trench inspection ###-#### this permit got finaled as a temp pole when actually the temp pole permit number is ele02-03819. This permit is for the whole job and should not be finaled. The other one should. ok 1/22/2003 9:57:30 AM
ELE03-00148 Rough-In Permanent Service1/21/20031/22/20031/22/2003 12:00:00 AMAPART
dave; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 1/22/2003 11:38:22 AM
ELE03-00161 Final1/22/20031/22/20031/22/2003 12:00:00 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Joe Thomas no final see added inspection 1/22/2003 12:15:53 PM
ELE03-00182 Rough-In Permanent Service1/22/20031/22/20031/22/2003 12:00:00 AMPPASS
EMMETT ###-#### r/i ok


p/s u/g new ok 1/22/2003 1:02:25 PM
ELE03-00067 Electrical Rough-In1/22/20031/22/20031/22/2003 12:00:00 AMPPART
T J (TO INSPECT THE TRENCH FOR BACK FILL); Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 1/22/2003 9:37:08 AM
ELE02-00309 Final1/22/20031/22/20031/22/2003 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok 1/22/2003 4:38:37 PM
ELE03-00184 Rough-In Permanent Service1/22/20031/22/20031/22/2003 12:00:00 AMPFAIL
###-####- jim cor. posted called 210.52(B)&210.23(A) exception remove vacuum outlet from kit. circuit 250.148 (A) grd box upstairs hallway, 334.30&314.17(C) staple romex at all boxes, note install mudring switch dinning rm 1/22/2003 2:00:51 PM
ELE02-03634 Final1/22/20031/22/20031/22/2003 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. posted called 314.16&334.15 needs proper size boxes and protect cable island counter 1/22/2003 2:54:24 PM
ELE03-00157 Final1/22/20031/22/20031/22/2003 12:00:00 AMPFAIL
tom--call 1st before insp -for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie owner will secure electrical contractor owner did not do work job is a basket case , owner permit will be canceled expired 1/22/2003 3:28:37 PM
ELE03-00161 Permanent Service1/22/20031/22/20031/22/2003 12:00:00 AMPPASS
no r/i cor. posted 300.4 11/4 for cables 110.12(A) replace plastic box with extra ko broken out called left message

p/s u/g new ok