BLD03-02168
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | PASS |
|
|
mike ; Phone #: 573-047 Fire life safety is OK. Per John with Comfort Air the HVAC unit is 5 ton 2000cfm unit and does not require automatic shutdown 1/22/2004 9:40:15 AM
|
BLD03-00686
| FIRE-Conference | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | DONE |
|
|
Inspection was for placement of duct smoke detectors in the mechanical room. Due to placement restrictions they will need a flow tester for the air through the chamber for verification of proper flow 1/22/2004 9:22:48 AM
|
BLD03-02861
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 1/22/2004 10:31:49 AM
|
BLD03-02344
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 1/22/2004 10:32:07 AM
|
BLD03-02348
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 1/22/2004 10:32:26 AM
|
BLD03-02674
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | FAIL |
|
|
Owner needs to provide data sheet on the fire proofing spray used on the wood panels above the ceiling 1/22/2004 10:33:19 AM
|
BLD99-03216
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | FAIL |
|
|
Need the security system/fire alarm drawings issued and inspected. All other life safety items are ok 1/22/2004 10:34:51 AM
|
BLD03-02931
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | PASS |
|
|
fire life safety OK 1/22/2004 11:02:18 AM
|
BLD03-01928
| FIRE-Final Inspection | 1/22/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety OK
|
FIR04-00014
| INSP-Alarm Testing | 1/20/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | A | CANC |
|
|
BILLY; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD03-01530
| FIRE-Final Inspection | 1/21/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | P | FAIL |
|
|
clint; Phone #: ###-#### Provide handle on the fire extinguisher cabinet door in the cafateria. Rated service door into the dishwashing area does not seal. Repair door holder that does not release 1/22/2004 3:44:08 PM
|
BLD03-02820
| FIRE-Final Inspection | 1/22/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety ok. Structural inspector please verify correct door hardware has been installed. Herb has the wrong type on at this time. 1/22/2004 1:44:15 PM
|
FIR03-00764
| INSP-Final Inspection | 1/22/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | P | FAIL |
|
|
It appears that the upright sprinkler heads on the asian market side of new rated wall. The new pendant heads exceed the 129 sq. ft. max spacing as noted on the drawings. Hangers need to be attached to the top chord of the trusses or engineer approved 1/22/2004 2:25:31 PM
|
BLD03-01927
| FIRE-Final Inspection | 1/22/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled
|
FIR03-00480
| INSP-Sprinkler Rough-in | 1/22/2004 | 1/22/2004 | 1/22/2004 12:00:00 AM | P | PART |
|
|
both day rooms, laundry room and sewing room are ok to cover the sprinkler piping 1/22/2004 1:15:16 PM
|