Inspections for the day of: Thursday, January 22, 2004.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02168 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMAPASS
mike ; Phone #: 573-047 Fire life safety is OK. Per John with Comfort Air the HVAC unit is 5 ton 2000cfm unit and does not require automatic shutdown 1/22/2004 9:40:15 AM
BLD03-00686 FIRE-Conference1/21/20041/22/20041/22/2004 12:00:00 AMADONE
Inspection was for placement of duct smoke detectors in the mechanical room. Due to placement restrictions they will need a flow tester for the air through the chamber for verification of proper flow 1/22/2004 9:22:48 AM
BLD03-02861 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMAPASS
Fire life safety finaled 1/22/2004 10:31:49 AM
BLD03-02344 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMAPASS
Fire life safety finaled 1/22/2004 10:32:07 AM
BLD03-02348 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMAPASS
Fire life safety finaled 1/22/2004 10:32:26 AM
BLD03-02674 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMAFAIL
Owner needs to provide data sheet on the fire proofing spray used on the wood panels above the ceiling 1/22/2004 10:33:19 AM
BLD99-03216 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMAFAIL
Need the security system/fire alarm drawings issued and inspected. All other life safety items are ok 1/22/2004 10:34:51 AM
BLD03-02931 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMAPASS
fire life safety OK 1/22/2004 11:02:18 AM
BLD03-01928 FIRE-Final Inspection1/22/20041/22/20041/22/2004 12:00:00 AMAPASS
Fire life safety OK
FIR04-00014 INSP-Alarm Testing1/20/20041/22/20041/22/2004 12:00:00 AMACANC
BILLY; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD03-01530 FIRE-Final Inspection1/21/20041/22/20041/22/2004 12:00:00 AMPFAIL
clint; Phone #: ###-#### Provide handle on the fire extinguisher cabinet door in the cafateria. Rated service door into the dishwashing area does not seal. Repair door holder that does not release 1/22/2004 3:44:08 PM
BLD03-02820 FIRE-Final Inspection1/22/20041/22/20041/22/2004 12:00:00 AMPPASS
Fire life safety ok. Structural inspector please verify correct door hardware has been installed. Herb has the wrong type on at this time. 1/22/2004 1:44:15 PM
FIR03-00764 INSP-Final Inspection1/22/20041/22/20041/22/2004 12:00:00 AMPFAIL
It appears that the upright sprinkler heads on the asian market side of new rated wall. The new pendant heads exceed the 129 sq. ft. max spacing as noted on the drawings. Hangers need to be attached to the top chord of the trusses or engineer approved 1/22/2004 2:25:31 PM
BLD03-01927 FIRE-Final Inspection1/22/20041/22/20041/22/2004 12:00:00 AMPPASS
Fire life safety finaled
FIR03-00480 INSP-Sprinkler Rough-in1/22/20041/22/20041/22/2004 12:00:00 AMPPART
both day rooms, laundry room and sewing room are ok to cover the sprinkler piping 1/22/2004 1:15:16 PM