Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01438 ELE-Aging Inspection1/22/20071/22/20071/23/2007 4:46:03 PM PART
called wsuc
ELE05-03669 ELE-Aging Inspection1/22/20071/22/20071/23/2007 8:07:38 AM PART
wsuc
ELE07-00066 Permanent Service1/22/20071/22/20071/22/2007 3:36:54 PMPFAIL
Phone #: ###-#### corr. called 310.15 (B)(2)(a) table derate conductors, 312.5(C) shall insyall cables as code noted states ,or install conductors in pvc to a Jbox under house then splice to romex, 250.148 splice and grd equip grd in jbox in house (old panel used as jbox), 408.8 panel schedule shall be specific location purpose and use
ELE06-04433 Electrical Rough-In1/19/20071/22/20071/22/2007 2:18:59 PMPPART
CONTACT: JASON MARTINEAU - CEILING INSPECTION PLEASE Phone #: ###-#### ok anop
ELE06-01341 Electrical Rough-In1/22/20071/22/20071/22/2007 1:45:09 PMPPART
bill; Phone #: ###-#### Internet Inspection Request from: Victoria Beall u/g across parking lot ok
ELE06-03684 Final1/22/20071/22/20071/22/2007 1:24:07 PMPPASS
linda - call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE06-03513 Final1/22/20071/22/20071/22/2007 11:58:05 AMPPASS
Morgan ###-#### final ok
ELE06-04306 Final1/18/20071/22/20071/22/2007 10:37:48 AMAPASS
READY FOR REINSPECTION. HOMEOWNERS WILL BE HOME MONDAY JANUARY 22, A.M.
THANKS Phone #: ###-#### ok
ELE06-03345 Final1/21/20071/22/20071/22/2007 10:37:26 AMAPASS
ok
ELE07-00151 Final1/19/20071/22/20071/22/2007 9:49:07 AMAPASS
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
lights ok
ELE06-03647 Final1/22/20071/22/20071/22/2007 9:20:19 AMAPASS
Scheduled by a contractor via Hello! on 1/22/2007 at 6:42:12 AM. ok
ELE07-00094 Permanent Service1/21/20071/22/20071/22/2007 8:58:58 AMAFAIL
Phone #: ###-#### corr. called 250.24(A)(1)terminate all GEC to neutral bus, 250.58 all grd electrodes shall tie togrther to form a common grd electrode system, ID meters
ELE07-00161 Rough-In Permanent Service1/19/20071/22/20071/22/2007 8:13:12 AMAPART
Requesting a uffer inspection. Phone #: ###-#### ok