FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 1/19/2007 | 1/22/2007 | 1/22/2007 4:42:23 PM | P | PART |
|
|
Inspection for overhead rough-in at the 4th floor SW quad is acceptable pending the installation of missing retaining straps at several locations on branch lines and arm-overs in the SW corner of this quadrant, hydrostatic test for the south half of the 4th floor passed.
|
FIR06-00910
| INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 4:39:17 PM | P | FAIL |
|
|
Pendent head at the main entry is not correctly installed, provide consistent temp. ratings of sprinklers installed at common fire areas, rough-in at the kitchen drop ceilings is good for cover.
|
FIR06-00782
| INSP-Sprinkler Rough-in/Hydro | 1/22/2007 | 1/22/2007 | 1/22/2007 4:00:29 PM | P | PART |
|
|
OH hydrostatic test is satisfactory, noted one head in the riser room to be changed to an intermediate temp. due to high ambient heat conditions, as-built plans need to reflect deletion of the SW heads at garage doors no longer of the overhead type, need to complete forward flow prior to final approval.
|
FIR06-00451
| INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 3:56:38 PM | P | FAIL |
|
|
The flow switch is not powered or connected to the outside bell as required.
|
FIR06-00954
| INSP-Sprinkler Rough-in/Hydro | 1/19/2007 | 1/22/2007 | 1/22/2007 2:33:41 PM | P | CANC |
|
|
Overbooked, no time available to complete this inspection today. Notified contact to reschedule per phone conversation.
|
FIR06-00920
| INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 2:31:12 PM | P | FAIL |
|
|
The PIV tamper switch is not correctly installed or adjusted, also lacking NFPA 72 record of inspeciton and testing to be completed (per review comments) prior scheduling final field acceptance test.
|
FIR06-00660
| INSP-Final Inspection | 1/18/2007 | 1/22/2007 | 1/22/2007 2:25:28 PM | A | FAIL |
|
|
The PIV tamper switch is not installed correctly, contractor to provide means for testing forward flow.
|
FIR06-00660
| INSP-Sprinkler Rough-in/Hydro | 1/18/2007 | 1/22/2007 | 1/22/2007 2:18:04 PM | A | PART |
|
|
UG fire supply line hydrostatic test passed inspection.
|
FIR06-00983
| INSP-Sprinkler Rough-in | 1/19/2007 | 1/22/2007 | 1/22/2007 1:36:23 PM | A | PART |
|
|
Fire sprinkler rough-in at the grid ceiling areas are good for cover.
|
FIR06-00024
| INSP-Sprinkler Rough-in/Hydro | 1/19/2007 | 1/22/2007 | 1/22/2007 11:10:48 AM | A | DEFR |
|
|
Wrong permit number called in for inspection by the contractor, was intended for FIR06-00782 Guerdon warehouse hydro and OH rough-in.
|
FIR06-00449
| INSP-Sprinkler Rough-in | 1/19/2007 | 1/22/2007 | 1/22/2007 10:26:42 AM | A | PART |
|
|
OH rough-in for building A-1 wet and antifreeze systems is satisfactory. Contractor also completed UG supply line hydrostatic test acceptable.
|
FIR06-01018
| INSP-Final Inspection | 1/19/2007 | 1/22/2007 | 1/22/2007 9:48:09 AM | A | PART |
|
|
Fire sprinkler work at the drop ceilings within the TI space are approved for cover.
|
MIS06-00336
| FIR-Final | 1/19/2007 | 1/22/2007 | 1/22/2007 9:26:13 AM | A | PASS |
|
|
Fire life safety final inspeciton passed.
|
MIS06-00335
| FIR-Final | 1/19/2007 | 1/22/2007 | 1/22/2007 9:25:41 AM | A | PASS |
|
|
Fire life safety inspection passed.
|
MIS06-00334
| FIR-Final | 1/19/2007 | 1/22/2007 | 1/22/2007 9:25:13 AM | A | PASS |
|
|
Fire life safety finaled.
|
FIR06-00954
| INSP-Sprinkler Rough-in/Hydro | 1/19/2007 | 1/22/2007 | 1/19/2007 3:56:26 PM | A | CANC |
|
|
Bret; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt Inspection cancelled from web by: Victoria Beall
|
FIR06-00851
| INSP-Final Inspection | 1/19/2007 | 1/22/2007 | 1/19/2007 1:21:53 PM | A | CANC |
|
|
Phone #: ###-#### Inspection cancelled from web by: Terry Owsley
|