Inspections for the day of: Monday, January 22, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00964 INSP-Sprinkler Rough-in1/22/20071/22/20071/23/2007 10:17:05 AMPFAIL
Provide resubmittals for the first floor area south of the bays. Relocate the branchline on the second floor south of the sky lights to within 6" center line of the peak and make the sprinkler deflectors horizontal. Provide approved hangers and hanging method for the 4" main piping in the bay area.
FIR06-00723 FIR-Aging Inspection1/22/20071/22/20071/23/2007 7:18:33 AM NR
work is in progress
FIR06-00843 INSP-Sprinkler Rough-in/Hydro1/22/20071/22/20071/22/2007 4:03:06 PMPFAIL
above ground hydrotest failed
FIR06-00955 INSP-Supply line flush1/22/20071/22/20071/22/2007 3:34:33 PMPFAIL
This was for an underground inspection.The underground supply piping is not buried below 4'-6" as required. Top of pipe is at 3'-10"
BLD06-03009 FIRE-Final Inspection1/22/20071/22/20071/22/2007 3:30:08 PMPPASS
life safety finaled
FIR06-00841 INSP-Sprinkler Rough-in/Hydro1/22/20071/22/20071/22/2007 3:05:16 PMPFAIL
Hydro test failed
FIR06-00938 INSP-Sprinkler Rough-in1/22/20071/22/20071/22/2007 3:00:29 PMPFAIL
See the city approved plans for the corrects required as marked in red. This includes the repairing of the insulation which is blocking the upright sprinklersPiping is not to be covered.
BLD06-03287 FIRE-Final Inspection1/22/20071/22/20071/22/2007 2:44:54 PMPFAIL
Repair the center areas exit sign and emergency light. Relocate the north fire extinguisher as discussed and test the three existing duct smoke detectors.
FIR06-00977 INSP-Sprinkler Rough-in/Hydro1/22/20071/22/20071/22/2007 2:26:37 PMPFAIL
Need additional sprinkler coverage in the southeast corner of the attic and the sway bracing installed on the 2" main. Also the 2x4 trapeze bracing can not be used for the 4" main. This inspection was for the south wing only.
BLD05-01063 FIRE-Final Inspection1/19/20071/22/20071/22/2007 1:34:17 PMAPASS
life safety finaled
FIR05-00799 INSP-Final Inspection1/22/20071/22/20071/22/2007 1:33:54 PMPPASS
permit finaled
FIR05-00693 INSP-Final Inspection1/22/20071/22/20071/22/2007 1:33:33 PMPPASS
permit finaled
FIR05-00827 INSP-Final Inspection1/19/20071/22/20071/22/2007 1:32:48 PMAPASS
life safety finaled
BLD05-02073 FIRE-Final Inspection1/19/20071/22/20071/22/2007 1:32:12 PMAPASS
permit finaled
FIR05-00800 INSP-Final Inspection1/22/20071/22/20071/22/2007 1:31:23 PMPPASS
permit finaled
MIS07-00007 FIR-Final1/19/20071/22/20071/22/2007 10:35:07 AMAPART
A temporary occupancy was given until the fire extinguishers are tagged and lowered to 48", provide sticker at the main exit, repair the emergency light in the warehouse and remove the deadbolts from the three interior doors
MIS06-00338 FIR-Final1/19/20071/22/20071/22/2007 10:01:49 AMAPASS
life safety finaled
BLD06-03074 FIRE-Final Inspection1/19/20071/22/20071/22/2007 9:45:35 AMAPASS
life safety finaled
FIR07-00005 INSP-Final Inspection1/22/20071/22/20071/22/2007 9:45:02 AMPPASS
permit finaled