FIR06-00964
| INSP-Sprinkler Rough-in | 1/22/2007 | 1/22/2007 | 1/23/2007 10:17:05 AM | P | FAIL |
|
|
Provide resubmittals for the first floor area south of the bays. Relocate the branchline on the second floor south of the sky lights to within 6" center line of the peak and make the sprinkler deflectors horizontal. Provide approved hangers and hanging method for the 4" main piping in the bay area.
|
FIR06-00723
| FIR-Aging Inspection | 1/22/2007 | 1/22/2007 | 1/23/2007 7:18:33 AM | | NR |
|
|
work is in progress
|
FIR06-00843
| INSP-Sprinkler Rough-in/Hydro | 1/22/2007 | 1/22/2007 | 1/22/2007 4:03:06 PM | P | FAIL |
|
|
above ground hydrotest failed
|
FIR06-00955
| INSP-Supply line flush | 1/22/2007 | 1/22/2007 | 1/22/2007 3:34:33 PM | P | FAIL |
|
|
This was for an underground inspection.The underground supply piping is not buried below 4'-6" as required. Top of pipe is at 3'-10"
|
BLD06-03009
| FIRE-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 3:30:08 PM | P | PASS |
|
|
life safety finaled
|
FIR06-00841
| INSP-Sprinkler Rough-in/Hydro | 1/22/2007 | 1/22/2007 | 1/22/2007 3:05:16 PM | P | FAIL |
|
|
Hydro test failed
|
FIR06-00938
| INSP-Sprinkler Rough-in | 1/22/2007 | 1/22/2007 | 1/22/2007 3:00:29 PM | P | FAIL |
|
|
See the city approved plans for the corrects required as marked in red. This includes the repairing of the insulation which is blocking the upright sprinklersPiping is not to be covered.
|
BLD06-03287
| FIRE-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 2:44:54 PM | P | FAIL |
|
|
Repair the center areas exit sign and emergency light. Relocate the north fire extinguisher as discussed and test the three existing duct smoke detectors.
|
FIR06-00977
| INSP-Sprinkler Rough-in/Hydro | 1/22/2007 | 1/22/2007 | 1/22/2007 2:26:37 PM | P | FAIL |
|
|
Need additional sprinkler coverage in the southeast corner of the attic and the sway bracing installed on the 2" main. Also the 2x4 trapeze bracing can not be used for the 4" main. This inspection was for the south wing only.
|
BLD05-01063
| FIRE-Final Inspection | 1/19/2007 | 1/22/2007 | 1/22/2007 1:34:17 PM | A | PASS |
|
|
life safety finaled
|
FIR05-00799
| INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 1:33:54 PM | P | PASS |
|
|
permit finaled
|
FIR05-00693
| INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 1:33:33 PM | P | PASS |
|
|
permit finaled
|
FIR05-00827
| INSP-Final Inspection | 1/19/2007 | 1/22/2007 | 1/22/2007 1:32:48 PM | A | PASS |
|
|
life safety finaled
|
BLD05-02073
| FIRE-Final Inspection | 1/19/2007 | 1/22/2007 | 1/22/2007 1:32:12 PM | A | PASS |
|
|
permit finaled
|
FIR05-00800
| INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 1:31:23 PM | P | PASS |
|
|
permit finaled
|
MIS07-00007
| FIR-Final | 1/19/2007 | 1/22/2007 | 1/22/2007 10:35:07 AM | A | PART |
|
|
A temporary occupancy was given until the fire extinguishers are tagged and lowered to 48", provide sticker at the main exit, repair the emergency light in the warehouse and remove the deadbolts from the three interior doors
|
MIS06-00338
| FIR-Final | 1/19/2007 | 1/22/2007 | 1/22/2007 10:01:49 AM | A | PASS |
|
|
life safety finaled
|
BLD06-03074
| FIRE-Final Inspection | 1/19/2007 | 1/22/2007 | 1/22/2007 9:45:35 AM | A | PASS |
|
|
life safety finaled
|
FIR07-00005
| INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 9:45:02 AM | P | PASS |
|
|
permit finaled
|