Inspections for the day of: Tuesday, January 22, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02246 FIRE-Final Inspection1/22/20081/22/20081/22/2008 4:27:04 PMPPASS
life safety passed.
FIR08-00010 INSP-Final Inspection1/18/20081/22/20081/22/2008 4:25:52 PMPPASS
permit finaled
FIR08-00008 INSP-Final Inspection1/18/20081/22/20081/22/2008 3:02:02 PMPPASS
Permit finaled
FIR07-00916 INSP-Final Inspection1/22/20081/22/20081/22/2008 3:01:16 PMPFAIL
The ceiling mounted strobes in the open areas are blocked by duct work and will need to be located where they are visable. All of the wall mounted strobes are mounted too low to meet code requirements. Atleast three of the duct smoke detectors will require manometer testing to verify location. The alarm tech stated that both of the phone lines were disabled. No test was performed.
BLD07-03062 FIRE-Final Inspection1/22/20081/22/20081/22/2008 1:18:54 PMPPASS
life safety passed
FIR07-01010 INSP-Final Inspection1/22/20081/22/20081/22/2008 1:18:34 PMPPASS
permit finaled
FIR07-00449 INSP-Sprinkler Rough-in1/21/20081/22/20081/22/2008 11:59:18 AMAPART
OH Cover inspection as far as the sprinkler piping installation is ok but alot of fire proofing has been damaged by all of the trades and will need to be repaired prior to the installation of the ceiling. I notified the superintendant of this.
FIR08-00010 INSP-Final Inspection1/18/20081/22/20081/18/2008 2:52:23 PMACANC
Scheduled by a contractor via Hello! on 1/18/2008 at 2:34:25 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 18 2008 2:52PM.