BLD07-02246
| FIRE-Final Inspection | 1/22/2008 | 1/22/2008 | 1/22/2008 4:27:04 PM | P | PASS |
|
|
life safety passed.
|
FIR08-00010
| INSP-Final Inspection | 1/18/2008 | 1/22/2008 | 1/22/2008 4:25:52 PM | P | PASS |
|
|
permit finaled
|
FIR08-00008
| INSP-Final Inspection | 1/18/2008 | 1/22/2008 | 1/22/2008 3:02:02 PM | P | PASS |
|
|
Permit finaled
|
FIR07-00916
| INSP-Final Inspection | 1/22/2008 | 1/22/2008 | 1/22/2008 3:01:16 PM | P | FAIL |
|
|
The ceiling mounted strobes in the open areas are blocked by duct work and will need to be located where they are visable. All of the wall mounted strobes are mounted too low to meet code requirements. Atleast three of the duct smoke detectors will require manometer testing to verify location. The alarm tech stated that both of the phone lines were disabled. No test was performed.
|
BLD07-03062
| FIRE-Final Inspection | 1/22/2008 | 1/22/2008 | 1/22/2008 1:18:54 PM | P | PASS |
|
|
life safety passed
|
FIR07-01010
| INSP-Final Inspection | 1/22/2008 | 1/22/2008 | 1/22/2008 1:18:34 PM | P | PASS |
|
|
permit finaled
|
FIR07-00449
| INSP-Sprinkler Rough-in | 1/21/2008 | 1/22/2008 | 1/22/2008 11:59:18 AM | A | PART |
|
|
OH Cover inspection as far as the sprinkler piping installation is ok but alot of fire proofing has been damaged by all of the trades and will need to be repaired prior to the installation of the ceiling. I notified the superintendant of this.
|
FIR08-00010
| INSP-Final Inspection | 1/18/2008 | 1/22/2008 | 1/18/2008 2:52:23 PM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 1/18/2008 at 2:34:25 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 18 2008 2:52PM.
|