Inspections for the day of: Thursday, January 22, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00688 FIR-Aging Inspection1/22/20091/22/20091/27/2009 10:28:50 AM NR
Work is still in progress per dave
FIR07-01032 INSP-Sprinkler Rough-in1/22/20091/22/20091/23/2009 3:35:52 PMPFAIL
The hydro test for the second floor skilled nursing dining area failed.
BLD08-01965 FIRE-Final Inspection1/21/20091/22/20091/22/2009 4:30:03 PMPFAIL
The project related fire sprinkler permit needs to be finaled and the two missing exit signs installed and tested.
FIR08-00642 INSP-Final Inspection1/21/20091/22/20091/22/2009 4:29:04 PMPFAIL
Standard responce and quick responce heads have been installed in the same area and one pendant is blocked by a suspended light fixture.
FIR08-00593 INSP-Alarm Testing1/21/20091/22/20091/22/2009 2:07:49 PMAPASS
Permit finaled
FIR08-00434 INSP-Final Inspection1/21/20091/22/20091/22/2009 1:17:45 PMAPASS
permit finaled
FIR08-00541 INSP-Final Inspection1/21/20091/22/20091/22/2009 1:13:26 PMAPASS
Permit finaled