Inspections for the day of: Friday, January 22, 2010.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00793 General Inspection1/22/20101/22/20101/22/2010 3:53:20 PMPPASS
looked ok
ESC08-00761 General Inspection1/22/20101/22/20101/22/2010 3:52:38 PMPPASS
looked ok
ELE08-03103 Final1/22/20101/22/20101/22/2010 3:50:17 PMPCANC
Chad Phone #: ###-#### called electrical contractor, he said homeowner did trim, called homeowner and told him that he has to get electrical permit to do wiring, and then to call in, told him to be sure his new permit gets grouped with other permits
ELE10-00005 Final1/21/20101/22/20101/22/2010 3:14:28 PMPCANC
Contact: Garrtt Collins, please call before going Phone #: ###-#### Internet Inspection Request from: Deb Gooden called contractor, power co. has not set meter yet, will recall, no esc this project
ELE09-02295 Electrical Rough-In1/22/20101/22/20101/22/2010 2:49:13 PMPPART
dan - late afternoon please Phone #: ###-#### 2nd bath only ok to cover, no esc this project
ELE09-02361 Final1/22/20101/22/20101/22/2010 2:04:31 PMPPASS
dan - late afternoon please Phone #: ###-#### called contractor, will add 1 room to permit, ok to final, no esc this project
ELE09-02348 Final1/22/20101/22/20101/22/2010 12:52:52 PMPCANC
eric - please call 1/2 hr prior Phone #: ###-#### see p/s
ELE09-02348 Permanent Service1/22/20101/22/20101/22/2010 12:52:13 PMPPASS
eric - please call 1/2 hr prior Phone #: ###-#### p/s, exst meter pak, n, ok, 2 meters required, no esc this project
ELE10-00049 Final1/22/20101/22/20101/22/2010 12:19:10 PMPFAIL
Allan Phone #: ###-#### called, left message, left correction notice, NEC 250.26 shall augment grounding electrode by 1 additional electrode, 408.4 shall clearly identify circuits on circuit directory, 352.30 shall secure pvc within 3' of box, no esc this project
ELE09-02005 Final1/22/20101/22/20101/22/2010 11:17:56 AMAPASS
looked at sign, ok to final, no esc this project
ELE08-02259 ELE-Aging Inspection1/22/20101/22/20101/22/2010 11:01:15 AM DONE
see final, no activity
ELE08-02259 Final1/22/20101/22/20101/22/2010 10:43:22 AMAPASS
no activity, ok to final
ELE08-02315 ELE-Aging Inspection1/22/20101/22/20101/22/2010 10:41:35 AM DONE
no activity, see doc expire
ELE08-02315 DOC - Permit Expired1/22/20101/22/20101/22/2010 10:41:22 AMAPASS
no activity, ok to doc expire
ELE10-00125 Rough-In Permanent Service1/21/20101/22/20101/22/2010 10:32:47 AMACANC
Justin Phone #: ###-#### see ri and p/s
ELE10-00125 Electrical Rough-In1/22/20101/22/20101/22/2010 9:56:16 AMAFAIL
Justin Phone #: ###-#### called, left message, left correction notice, NEC 334.30 shall secure nm cable within 12" of box, 210.52(A)(1) shall install receptacles such that no point along floor line is over 6' from an outlet- south entry room, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 110.12(B) there shall be no broken boxes-north part kitchen, 110.3(B) shall install listed equipment in accordance with instructions i.e. shall ensure that access to jetted tub is provide with 12"x24" opening, BCC shall provide boxes for under stair light, range, 240v circuit in basement
ELE10-00125 Permanent Service1/22/20101/22/20101/22/2010 9:26:43 AMAPASS
Justin Phone #: ###-#### p/s u/g n ok
ELE10-00124 Final1/22/20101/22/20101/22/2010 9:25:17 AMAPASS
ok to final, no esc this project
ELE10-00124 Electrical Rough-In1/21/20101/22/20101/22/2010 9:24:15 AMAPASS
Extended an existing 20 amp 120 volt isolated ground circuit #A-27 from the existing j-box in the back room thru the wall via LTNM flex to a new isolated ground receptacle inside the computer room. Please final this permit as we are done. See Carma for the tour. Dan ###-####. Thnks !!!! Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok
ELE10-00127 Rough-In Permanent Service1/22/20101/22/20101/22/2010 8:33:27 AMAPASS
thanks! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn called, left message, ric ok, p/s u/g n ok