Inspections for the day of: Friday, January 22, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03958 Permanent Service1/21/20161/22/20161/22/2016 2:35:25 PMPFAIL
We need a service inspection for IPCO to reconnect service. Thank you, Dale Phone #: ###-#### Inspection requested via web by Thomas Jenkins
110.22- Each disconnecting means shall be identified as to its purpose.
110.24- Available fault current chall be posted with date calculated prior to permanent service inspection. 250.90- Standard lock nuts and bushings shall not be only means of bonding service enclosures. bonding bushings required at all nipples.
300.4- Replace all bushings that are missing or damaged.
230.71- Max number of disconnecting means shall not exceed 6.
Drawing shows total load of 301 amp plus well at 40 amps on 500 KCMIL service entrance rated at 380 amps 75 degrees.
ELE16-00213 Final1/22/20161/22/20161/22/2016 12:29:37 PMPPASS
Phone #: ###-#### Inspection requested via web by Kyle Lott Final ok
ELE16-00213 Final1/22/20161/22/20161/22/2016 12:28:31 PMPPASS
Phone #: ###-#### Inspection requested via web by Kyle Lott Final ok
ELE13-01956 DOC - Permit Expired1/22/20161/22/20161/22/2016 11:27:54 AMPPASS
Work completed under ELE13-02014. Expired
ELE13-01940 Final1/22/20161/22/20161/22/2016 10:56:34 AMPPASS
Drove by and inspected. Labelling complete Final ok
ELE15-02845 Conference1/21/20161/22/20161/22/2016 10:44:45 AMADONE
Please call ahead for access - Shawn Phone #: ###-#### Discussed kitchen area, outlet spacing, max circuit load for appliances, dedicated bathroom receptacle circuit, approved boxes and covers for receptacles install in counter top. Discussed service location and type for future 2nd floor apartment.
Called and asked Brittney to attach to BLD15-01818
ELE16-00017 Final1/21/20161/22/20161/22/2016 10:01:47 AMAPASS
Bob Phone #: ###-#### Final ok
ELE15-03503 Final1/21/20161/22/20161/22/2016 9:40:56 AMAFAIL
Garage code is 6767 Phone #: ###-#### Inspection requested via web by TOM BICANDI
110.3- Breaker lockout shall be secured to overcurrent device as per manufacturers instructions.
314.21- Drywall shall be repaired around garage outlet and remove build up of mud so panel cover fits flush.
410.16(C)- Closet luminaire with incondscent lamp shall not be installed less than 12" from shelf. Up bed