Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05047 Final1/18/20191/22/20191/22/2019 11:34:03 AMAFAIL
Please call Russ, Thank YOU!! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Need to install sediment trap after shutoff valve and before regulator. Need to install test port after the regulator. The roof hatch is required to have a guardrail per code section 304.11 IMC.
MEC19-00258 Rough-in1/18/20191/22/20191/22/2019 10:13:35 AMAPART
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth - Light test pass on 2 straight sections of grease duct in the T.I. space and 1 off set straight section in the T. I. space