BLD97-00698
| INSP-Sprinkler Rough-in/Hydro | 1/23/1998 | 1/23/1998 | 1/23/1998 12:00:00 AM | A | PASS |
|
|
rough-in okay. hydro okay. water temp of circulating system between 100-110.
|
BLD97-01426
| INSP-Final Inspection | 1/22/1998 | 1/23/1998 | 1/23/1998 12:00:00 AM | A | FAIL |
|
|
trip test of dry sprinkler system - okay. sprinkler system now has over 100 heads, not monitored. no outside control valve.
|
BLD97-01426
| INSP-Sprinkler Rough-in/Hydro | 1/22/1998 | 1/23/1998 | 1/23/1998 12:00:00 AM | P | PASS |
|
|
hydro passed.
|
BLD97-01243
| INSP-Sprinkler Rough-in/Hydro | 1/22/1998 | 1/23/1998 | 1/23/1998 12:00:00 AM | P | PASS |
|
|
PROBLEM CALL SHELLIE AT ###-#### time changed to 1:00 pm per inspector and contractor request basement rough-in only. okay to cover. additional head needed in southwest room to cover area missed by sidewall.
|
BLD97-00698
| INSP-Sprinkler Rough-in/Hydro | 1/23/1998 | 1/23/1998 | 1/23/1998 12:00:00 AM | P | PASS |
|
|
hydro of dry standpipe system - had to repair leak at basement - okay after repair.
|