BLD02-02367
| FIRE-Final Inspection | 1/20/2003 | 1/23/2003 | 1/24/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 01/20/2003 at 13:40:16. Contact: ###-####. door was sticking on carpet and is fixed according to GC; alarm tested and okay; card not there to sign off 1/24/2003 8:17:42 AM
|
MIS03-00013
| FIR-Final | 1/22/2003 | 1/23/2003 | 1/23/2003 12:00:00 AM | A | FAIL |
|
|
###-#### mike matzek room is used for meeting room with 2nd exit through storage area separated by curtain; called Jason and he said to have owner resubmit and declare use 1/23/2003 9:48:55 AM
|
FIR02-00506
| INSP-Final Inspection | 1/16/2003 | 1/23/2003 | 1/23/2003 12:00:00 AM | A | PASS |
|
|
robert--call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIR02-00436
| INSP-Sprinkler Rough-in | 1/23/2003 | 1/23/2003 | 1/23/2003 12:00:00 AM | P | PART |
|
|
underground complete; okay to cover
|
FIR01-00491
| INSP-Final Inspection | 1/22/2003 | 1/23/2003 | 1/23/2003 12:00:00 AM | P | PASS |
|
|
###-####
|
FIR00-00668
| INSP-Final Inspection | 1/22/2003 | 1/23/2003 | 1/23/2003 12:00:00 AM | P | FAIL |
|
|
###-#### duct detectors weren't shown on plans/map and inspector will need to test for unit shutdown; knox box needed per plan review notes; need written plan to Dave Miller for elevator recall; provide map at panel and show relocation of FACP and NAC panels; duct detectors need remote LED's or signs on grid to show location 1/23/2003 5:25:41 PM
|
FIR02-00408
| INSP-Alarm Testing | 1/22/2003 | 1/23/2003 | 1/23/2003 12:00:00 AM | P | CANC |
|
|
test; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino dan was testing the internet process for requesting inspections 1/23/2003 7:54:25 AM
|