BLD03-01318
| BLD-Aging Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | | PASS |
|
|
|
FIR04-00013
| INSP-Final Inspection | 1/22/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | A | NR |
|
|
10 am per Billy per Billy this will be rescheduled for next week 1/23/2004 10:31:21 AM
|
BLD03-02346
| FIRE-Final Inspection | 1/22/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/22/2004 at 10:07:56 AM. Contact: ###-####.
|
BLD03-02558
| FIRE-Final Inspection | 1/22/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | A | PASS |
|
|
Dean; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD02-02853
| FIRE-Final Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | A | FAIL |
|
|
need exit signs as shown on plans for second floor; repair exit sign on second floor at SW exit stair (needs battery backup); need occupant load sign in room 139; lever hardware on stair/exit doors; clear stairs of materials; smoke seals on stair doors;eed fire extinguishers throughout; need signs on riser room and FACP room doors 1/23/2004 9:03:19 AM
|
FIR03-00426
| INSP-Final Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | A | FAIL |
|
|
need escutcheons on several sprinler heads; riser requires annual inspection; need sign on riser room door 1/23/2004 9:00:15 AM
|
FIR04-00023
| DOC - Permit Finaled | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | CANC |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIR04-00023
| INSP-Final Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | FAIL |
|
|
need hanger on one armover; see plans 1/23/2004 3:38:01 PM
|
FIR03-00793
| INSP-Final Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | PART |
|
|
JOHN; Phone #: ###-#### Internet Inspection Request from: Annette Moore okay to cover areas as highlighted on plans; need resubmittals for 2 inch mofications 1/23/2004 3:11:21 PM
|
BLD03-01318
| FIRE-Final Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | PASS |
|
|
|
BLD03-01468
| FIRE-Final Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | PASS |
|
|
no occupancy card on site so put final on inspection record card; fire/life safety okay 1/23/2004 4:23:36 PM
|
FIR03-00318
| INSP-Final Inspection | 1/22/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | PASS |
|
|
JASON; Phone #: ###-#### Internet Inspection Request from: Darla Downs local alarm only; battery charger can handle batteries up to 36 amp per manufacturer 1/23/2004 4:22:02 PM
|
BLD03-01902
| FIRE-Final Inspection | 1/22/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | FAIL |
|
|
STEVE; Phone #: ###-#### Internet Inspection Request from: Darla Downs need resubmittals for review prior to sign off 1/23/2004 2:07:42 PM
|
FIR02-00438
| INSP-Alarm Testing | 1/23/2004 | 1/23/2004 | 1/23/2004 12:00:00 AM | P | PASS |
|
|
cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
|