Inspections for the day of: Monday, January 23, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02060 ELE-Aging Inspection1/23/20061/23/20061/27/2006 8:29:00 AM NR
called contractor
suc
ELE06-00241 Electrical Rough-In1/20/20061/23/20061/23/2006 4:15:59 PMPPASS
Bob ###-####
switch in wall at entrance ceiling ok
ELE03-02903 ELE-Aging Inspection1/23/20061/23/20061/23/2006 3:22:59 PM NR
suc
ELE05-01974 ELE-Aging Inspection1/23/20061/23/20061/23/2006 3:00:59 PM NR
suc
ELE05-04589 Electrical Rough-In1/20/20061/23/20061/23/2006 3:00:42 PMPPART
Ed; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
walls and hard lids ok
ELE06-00257 Rough-In Permanent Service1/23/20061/23/20061/23/2006 1:14:59 PMPPASS
Mark ###-####
P/S U/G N Ok
R/I Ok
no approved print check for required outlets on final
ELE05-03887 Final1/20/20061/23/20061/23/2006 11:31:30 AMAPASS
Scheduled by a contractor via Hello! on 1/20/2006 at 11:15:47 AM. Contact: ###-####.
no card
ELE05-02578 Final1/20/20061/23/20061/23/2006 10:58:41 AMANH
final on kitchen remodel Internet Inspection Request from: Andy Rose
no answer to door
ELE06-00237 Final1/20/20061/23/20061/23/2006 10:58:04 AMAPASS
circuit for computer and heater Internet Inspection Request from: Andy Rose
ELE06-00193 Final1/20/20061/23/20061/23/2006 10:09:18 AMAFAIL
need inspection on hot tub and recessed can lighting. Call homeowner @###-#### to set time so she can be there to let you in Internet Inspection Request from: Andy
Rose
400.8 Uses Not Permitted.
Unless specifically permitted in 400.7, flexible cords and cables shall not be used for the following:
Cord not permitted for direct burial.
300.5 Underground Installations
(A) Minimum Cover Requirements Direct-buried cable or conduit or other raceways shall be installed to meet the minimum cover requirements of Table 300.5.
358.10 Uses Permitted
(B) Corrosion Protection Ferrous or nonferrous EMT, elbows, couplings, and fittings shall be permitted to be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable for the condition.
680.22 Area Lighting, Receptacles, and Equipment
(A) Receptacles
(2) Other Receptacles, Location Other receptacles shall be not less than 3.0 m (10 ft) from the inside walls of a pool.
(5) GFCI Protection All 15- and 20-ampere, single-phase, 125-volt receptacles located within 6.0 m (20 ft) of the inside walls of a pool shall be protected by a ground-fault circuit interrupter. Receptacles that supply pool pump motors and that are rated 15 or 20 amperes, 125 volts through 250 volts, single phase, shall be provided with GFCI protection.
680.8 Overhead Conductor Clearances
Overhead conductors shall meet the clearance requirements in this section. Where a minimum clearance from the water level is given, the measurement shall be taken from the maximum water level of the specified body of water.
ELE06-00247 Electrical Rough-In1/21/20061/23/20061/23/2006 10:00:16 AMAPART
Please call Mike at ###-#### to arrange entrance to building prior to inspection. Internet Inspection Request from: Steve Craig
east bathroom ok
ELE06-00211 Temporary Service1/20/20061/23/20061/23/2006 9:59:46 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
T/S U/G Ok
ELE05-04203 Final1/20/20061/23/20061/23/2006 8:13:03 AMAPASS
alan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
ELE05-04589 Electrical Rough-In1/20/20061/23/20061/20/2006 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 1/20/2006 at 1:05:06 PM. Contact: ###-####
1-20-06 needed PM insp/eus