Inspections for the day of: Monday, January 23, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02986 ELE-Aging Inspection1/23/20061/23/20061/23/2006 4:26:30 PM DONE
see final
ELE06-00150 Electrical Rough-In1/20/20061/23/20061/23/2006 4:08:40 PMPPART
Jeremiah; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to cover walls only so central and so side of bldg anop
ELE06-00113 Electrical Rough-In1/23/20061/23/20061/23/2006 3:37:43 PMPPART
CONTACT: LYLE DEAN; Phone #: ###-#### Internet Inspection Request from: Deb McCoy walls only 1st floor garage ok to cover anop
ELE05-03129 ELE-Aging Inspection1/23/20061/23/20061/23/2006 2:06:28 PM DONE
see final
ELE04-02606 ELE-Aging Inspection1/23/20061/23/20061/23/2006 2:02:08 PM DONE
see final
ELE06-00248 Electrical Rough-In1/23/20061/23/20061/23/2006 2:00:17 PMPPASS
POOL BONDING; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack pool bond only ok, no u/g seen
ELE06-00229 Temporary Service1/20/20061/23/20061/23/2006 10:21:12 AMAPASS
Brandon; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
ELE06-00230 Temporary Service1/20/20061/23/20061/23/2006 9:43:49 AMAFAIL
Brandon; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left message, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no damaged or broken parts
ELE06-00003 Final1/20/20061/23/20061/23/2006 9:39:43 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr, left corr notice, 210.11(C)(3) bathroom shall be on 20A ckt,210.12(A) bedroom shall be protected by AFCI, 110.3(B) equipment shall be installed and used in accordance with instructions
ELE06-00221 Final1/19/20061/23/20061/23/2006 9:16:17 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
ELE04-02606 Final1/23/20061/23/20061/23/2006 12:00:00 AMPDONE
ok to final, met with 315, said was done
ELE05-03129 Final1/23/20061/23/20061/23/2006 12:00:00 AMPPASS
looked at sign, ok to final
ELE05-02986 Final1/23/20061/23/20061/23/2006 12:00:00 AMPPASS
looked at signs, ok to final