ELE05-03806
| Final | 1/23/2007 | 1/23/2007 | 1/23/2007 4:42:01 PM | P | NH |
|
|
Randy; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt equipment room locked, elev contr out of time, decided to do inspection 1/24/07 am
|
ELE06-03451
| Rough-In Permanent Service | 1/10/2007 | 1/23/2007 | 1/23/2007 3:43:26 PM | P | CANC |
|
|
matt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see ri and ps
|
ELE06-03451
| Electrical Rough-In | 1/23/2007 | 1/23/2007 | 1/23/2007 3:43:06 PM | P | FAIL |
|
|
matt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met owner, service was ok, ri corrections are: nec 312.5 all conductors entering enclosures shall have abrasion protection, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from face of framing members, 110.12(C) there shall be no broken parts(boxes), 250.53(D)(2) supplementary grounding electrode shall be installed, 334.30 nm cable shall be supported within 12" of box and 8" for plastic, BCC all make-up shall be done
|
ELE06-04463
| Final | 1/23/2007 | 1/23/2007 | 1/23/2007 2:59:47 PM | P | PASS |
|
|
Phone #: ###-#### ok to final
|
ELE07-00236
| Electrical Rough-In | 1/23/2007 | 1/23/2007 | 1/23/2007 2:20:58 PM | P | PASS |
|
|
mike - please call 1/2 prior to inspection - underground ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover u/g
|
ELE07-00220
| Rough-In Permanent Service | 1/22/2007 | 1/23/2007 | 1/23/2007 2:20:07 PM | P | PASS |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr for some nail plates, ric ok p/s u/g n ok
|
ELE06-02468
| Permanent Service | 1/23/2007 | 1/23/2007 | 1/23/2007 1:55:14 PM | P | PASS |
|
|
CONTACT: JOHN STEBLY Phone #: ###-#### p/s u/g n ok
|
ELE06-03451
| Permanent Service | 1/23/2007 | 1/23/2007 | 1/23/2007 12:36:10 PM | P | PASS |
|
|
matt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g rec ok
|
ELE05-03578
| Final | 1/22/2007 | 1/23/2007 | 1/23/2007 10:36:10 AM | A | NH |
|
|
final inspection please Phone #: ###-#### called contr, told him nh, he will recall
|
ELE07-00214
| Final | 1/22/2007 | 1/23/2007 | 1/23/2007 9:58:54 AM | A | PASS |
|
|
Work performed by Ron Chaney. Phone #: ###-#### talked to elect about tester showing open gnd, ok to final
|
ELE05-00855
| Final | 1/22/2007 | 1/23/2007 | 1/23/2007 9:03:39 AM | A | PART |
|
|
Contact: Greg Pack - partial final-1st floor Phone #: ###-#### looked at new mech room for fire prot, told contr to find out about jockey pump listing, drip protection over panels, labels, need elev request for inspections
|
ELE07-00220
| Permanent Service | 1/22/2007 | 1/23/2007 | 1/23/2007 12:00:00 AM | A | CANC |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
ELE07-00220
| Electrical Rough-In | 1/22/2007 | 1/23/2007 | 1/22/2007 12:00:00 AM | A | CANC |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|