FIR06-00724
| FIR-Aging Inspection | 1/23/2007 | 1/23/2007 | 1/26/2007 2:51:37 PM | | NR |
|
|
work is in progress
|
BLD05-02052
| FIRE-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 4:17:30 PM | P | FAIL |
|
|
Provide fire extinguishers in each of the apartment units as discussed with annual inspection tags. Also provide fire dept signage or curb painting as discussed. Smoke detectors operated correctly.
|
BLD05-02962
| FIRE-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 4:16:30 PM | P | FAIL |
|
|
Provide fire extinguishers in each of the apartment units as discussed with annual inspection tags. Also provide fire dept signage or curb painting as discussed. Smoke detectors operated correctly.
|
BLD05-02051
| FIRE-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 3:56:32 PM | P | FAIL |
|
|
Provide fire extinguishers in each of the apartment units as discussed with annual inspection tags. Also provide fire dept signage or curb painting as discussed. Smoke detectors operated correctly.
|
FIR05-00425
| INSP-Sprinkler Rough-in | 1/22/2007 | 1/23/2007 | 1/23/2007 3:32:47 PM | A | CANC |
|
|
elisha; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Alicia Pauley
|
FIR06-00970
| INSP-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 3:14:18 PM | P | FAIL |
|
|
Brian did not have the approved plans. No inspection performed.
|
FIR06-00678
| INSP-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 3:13:34 PM | P | PASS |
|
|
Permit finaled. One sample tube had been installed backwards and was corrected while I waited.
|
FIR06-00910
| INSP-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 3:12:11 PM | P | FAIL |
|
|
Items noted on previous correction notice have been correct. Can not final until the ceiling tile has been installed. I notified Jim, the superintendent of this. He stated it would be done friday.
|
FIR06-00755
| INSP-Supply line flush | 1/22/2007 | 1/23/2007 | 1/23/2007 2:59:24 PM | A | PASS |
|
|
Underground flush passed for the west buildings.
|
BLD06-01671
| FIRE-Final Inspection | 1/22/2007 | 1/23/2007 | 1/23/2007 1:59:26 PM | P | FAIL |
|
|
No life safety inspected since the fire alarm failed and the sprinkler permit failed.
|
FIR06-00660
| INSP-Supply line flush | 1/23/2007 | 1/23/2007 | 1/23/2007 1:57:13 PM | P | FAIL |
|
|
forward flush passed but the backflow still needs certified and the alarm interconnections tested.
|
FIR06-00920
| INSP-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 1:56:01 PM | P | FAIL |
|
|
The fire alarm panel's display showed abunch of gibberish when testing phone line #2 and would not clear until all power had been dumped. Per Matt with Silent Knight technical support the panel should be replaced. The serial numbers on the existing panel mother bord are SN38273. These should change with a new board. Entire system will need to be tested.
|
FIR06-00954
| INSP-Sprinkler Rough-in/Hydro | 1/22/2007 | 1/23/2007 | 1/23/2007 1:43:03 PM | A | PASS |
|
|
The above ground hydro test was witnessed by Greg Bolton, the general contractor. System held 204 lbs for 2 hours. He agreed to sign the test papers. These test papers with his signature will be provided to the fire inspector at the next inspection.
|
FIR06-00843
| INSP-Sprinkler Rough-in/Hydro | 1/22/2007 | 1/23/2007 | 1/23/2007 12:53:34 PM | A | PASS |
|
|
Above ground hydro test passed.
|
FIR06-00841
| INSP-Sprinkler Rough-in/Hydro | 1/22/2007 | 1/23/2007 | 1/23/2007 12:52:18 PM | A | PASS |
|
|
Above ground hydro test passed.
|
FIR06-00582
| INSP-Final Inspection | 1/22/2007 | 1/23/2007 | 1/23/2007 11:42:50 AM | A | FAIL |
|
|
All items tested satifactory. A map at the facp or annunciator is all that is still required.
|
BLD06-03116
| FIRE-Final Inspection | 1/22/2007 | 1/23/2007 | 1/23/2007 11:17:53 AM | A | CANC |
|
|
per derrick the duct detector remote annunciator has not been wired yet. No inspection performed.
|
BLD06-03287
| FIRE-Final Inspection | 1/22/2007 | 1/23/2007 | 1/23/2007 11:03:47 AM | A | PASS |
|
|
life safety finaled
|
FIR06-00905
| INSP-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 10:26:32 AM | P | CANC |
|
|
Rafe''s phone Phone #: ###-#### Inspection cancelled from web by: Terry Owsley
|
FIR06-00964
| INSP-Sprinkler Rough-in | 1/22/2007 | 1/23/2007 | 1/23/2007 10:19:00 AM | A | PASS |
|
|
Hangers in the bay area have been corrected as well as the second floor area. Piping for the second floor and bay areas can be covered.
|