Inspections for the day of: Wednesday, January 23, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00091 INSP-Final Inspection1/23/20081/23/20081/25/2008 2:13:20 PMPFAIL
See 7 item correction notice and comments per inspection completed 1/24/08 for a list of items in need of revision.
BLD03-02347 FIRE-Final Inspection1/23/20081/23/20081/23/2008 3:39:54 PMPPASS
Noted one additional fire extinguisher to be posted as discussed due to excessive travel distances, provide approved door hardware or remove door at the SE call center area, items to be completed prior to structural final for verification at that time. Fire life safety for the permit scope area is acceptable pending completion of these two items.
BLD07-01689 FIRE-Final Inspection1/23/20081/23/20081/23/2008 2:57:40 PMPPASS
Fire life safety finaled.
FIR07-01039 INSP-Sprinkler Rough-in/Hydro1/23/20081/23/20081/23/2008 2:38:50 PMPPART
Completed overhead hydrostatic testing, inspection passed.
BLD07-01689 FIRE-Alarm Testing1/23/20081/23/20081/23/2008 2:29:18 PMPPASS
Project related fire alarm permit has been finaled.
FIR07-01039 INSP-Sprinkler Rough-in/Hydro1/22/20081/23/20081/23/2008 12:01:48 PMAPART
Overhead rough-in of the new system mains and branch lines is satisfactory, tie in pending hydro test completion, work in progress for demo of the old system piping and heads currently underway.
BLD07-01690 FIRE-Alarm Testing1/22/20081/23/20081/23/2008 11:56:15 AMANR
Inspection request intended for a different permit number.
FIR07-00956 INSP-Final Inspection1/22/20081/23/20081/23/2008 11:24:55 AMAPART
Project is not ready for final at this time, rough-in inspection completed and okayed for cover at the drop ceilings per the tenant remodel area, noted one ssu needs to be installed outside the tenant area to maintain the shell protection-marked location on approved plan set, also noted one main hanger at the corridor adjacent to the restrooms to be replaced as it was removed for ductwork install.
FIR04-00673 INSP-Alarm Testing1/22/20081/23/20081/23/2008 10:54:46 AMAPART
Smoke detectors in units 808 and 808 1/2 passed field testing, covers removed, locations are acceptable.
FIR06-00620 INSP-Alarm Testing1/17/20081/23/20081/23/2008 8:44:03 AMACANC
Please call 30 min prior to arrival Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
FIR07-00832 FIR-Aging Inspection1/23/20081/23/20081/23/2008 8:31:06 AM DEFR
In progress