BLD11-02578
| FIRE-Conference | 1/23/2012 | 1/23/2012 | 1/23/2012 3:18:57 PM | P | DONE |
|
|
I went over exit sign placement with the electrician. The superintendant and I went over the need to verify the wood above the ceiling as being fire rated.
|
FIR11-00014
| INSP-Conference | 1/23/2012 | 1/23/2012 | 1/23/2012 2:57:20 PM | P | DONE |
|
|
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
|
FIR12-00003
| INSP-Final Inspection | 1/23/2012 | 1/23/2012 | 1/23/2012 2:53:40 PM | P | PASS |
|
|
Permit finaled.
|
FIR11-00479
| INSP-Sprinkler Rough-in | 1/20/2012 | 1/23/2012 | 1/23/2012 2:53:10 PM | P | PASS |
|
|
All of the sprinkler piping in the new addition area located above the lay-in ceiling tile can be covered. The remodeled areas have not been inspected yet.
|
FIR11-00671
| INSP-Sprinkler Rough-in | 1/20/2012 | 1/23/2012 | 1/23/2012 1:55:49 PM | A | PASS |
|
|
The piping above the hardlid areas is ok to cover.
|
BLD12-00012
| FIRE-Conference | 1/20/2012 | 1/23/2012 | 1/23/2012 12:40:19 PM | A | DONE |
|
|
This conference was a request for a temporary occupancy due to the duct smoke detectors for two unit not being installed yet. I deferred the request to Romeo Gervais.
|
FIR11-00563
| INSP-Sprinkler Rough-in | 1/20/2012 | 1/23/2012 | 1/23/2012 12:38:23 PM | A | PASS |
|
|
See the city approved plans for locations at the west end of the fourth floor where the sprinkler piping can be covered.
|
FIR11-00688
| INSP-Alarm Testing | 1/20/2012 | 1/23/2012 | 1/23/2012 12:09:01 PM | A | FAIL |
|
|
A minimum reading of 19.6 volts could not be verified with the volt meter and it appears that there are more than three strobe rates.
|
FIR11-00683
| INSP-Alarm Testing | 1/20/2012 | 1/23/2012 | 1/23/2012 12:08:34 PM | A | FAIL |
|
|
A minimum reading of 19.6 volts could not be verified with the volt meter
|
BLD11-02927
| FIRE-Final Inspection | 1/20/2012 | 1/23/2012 | 1/23/2012 9:31:51 AM | A | FAIL |
|
|
Provide address numbers atleast 4" high and of a contrasting color.
|
FIR11-00688
| INSP-Sprinkler Rough-in/Hydro | 1/20/2012 | 1/23/2012 | 1/20/2012 11:38:13 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|