Inspections for the day of: Monday, January 23, 2012.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02578 FIRE-Conference1/23/20121/23/20121/23/2012 3:18:57 PMPDONE
I went over exit sign placement with the electrician. The superintendant and I went over the need to verify the wood above the ceiling as being fire rated.
FIR11-00014 INSP-Conference1/23/20121/23/20121/23/2012 2:57:20 PMPDONE
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
FIR12-00003 INSP-Final Inspection1/23/20121/23/20121/23/2012 2:53:40 PMPPASS
Permit finaled.
FIR11-00479 INSP-Sprinkler Rough-in1/20/20121/23/20121/23/2012 2:53:10 PMPPASS
All of the sprinkler piping in the new addition area located above the lay-in ceiling tile can be covered. The remodeled areas have not been inspected yet.
FIR11-00671 INSP-Sprinkler Rough-in1/20/20121/23/20121/23/2012 1:55:49 PMAPASS
The piping above the hardlid areas is ok to cover.
BLD12-00012 FIRE-Conference1/20/20121/23/20121/23/2012 12:40:19 PMADONE
This conference was a request for a temporary occupancy due to the duct smoke detectors for two unit not being installed yet. I deferred the request to Romeo Gervais.
FIR11-00563 INSP-Sprinkler Rough-in1/20/20121/23/20121/23/2012 12:38:23 PMAPASS
See the city approved plans for locations at the west end of the fourth floor where the sprinkler piping can be covered.
FIR11-00688 INSP-Alarm Testing1/20/20121/23/20121/23/2012 12:09:01 PMAFAIL
A minimum reading of 19.6 volts could not be verified with the volt meter and it appears that there are more than three strobe rates.
FIR11-00683 INSP-Alarm Testing1/20/20121/23/20121/23/2012 12:08:34 PMAFAIL
A minimum reading of 19.6 volts could not be verified with the volt meter
BLD11-02927 FIRE-Final Inspection1/20/20121/23/20121/23/2012 9:31:51 AMAFAIL
Provide address numbers atleast 4" high and of a contrasting color.
FIR11-00688 INSP-Sprinkler Rough-in/Hydro1/20/20121/23/20121/20/2012 11:38:13 AMACANC
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate