Inspections for the day of: Wednesday, January 23, 2013.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-02844 FIRE-Final Inspection1/23/20131/23/20131/23/2013 4:54:03 PMPPASS
Fire life safety inspection completed acceptable, previous correction items are finished.
FIR13-00025 INSP-Final Inspection1/23/20131/23/20131/23/2013 4:15:27 PMPPASS
Fire sprinkler rough-in and final inspections completed satisfactory. Permit finaled.
BLD12-02667 FIRE-Final Inspection1/22/20131/23/20131/23/2013 4:01:53 PMAFAIL
C/N items include; final open fire sprinkler permit, provide missing outside waterflow bell, keys at knox box, repair EM lights at the restroom corridor and basement levels, install EM lights per plan at the east and west exits, revise door hardware at four locations.
FIR12-00064 INSP-Final Inspection1/11/20131/23/20131/23/2013 3:26:38 PMAPASS
C/N items verified. Fire alarm permit finaled.
FIR13-00009 INSP-Final Inspection1/22/20131/23/20131/23/2013 3:25:42 PMAPASS
Fire alarm work passed inspection and testing. One adjustment made while on site, permit final approved.
FIR12-00061 INSP-Final Inspection1/11/20131/23/20131/23/2013 2:34:09 PMAPASS
Fire alarm work passed inspection and testing, permit finaled.
FIR12-00066 INSP-Final Inspection1/11/20131/23/20131/23/2013 2:33:01 PMAPASS
Verified points map has been posted. Fire alarm permit finaled.
FIR12-00088 INSP-Final Inspection1/11/20131/23/20131/23/2013 2:31:47 PMAPASS
Verified correction notice items have been finished. Fire alarm permit finaled.
FIR13-00023 INSP-Sprinkler Rough-in1/22/20131/23/20131/23/2013 12:29:56 PMAPART
Refer to the stamped plan set for areas marked and dated okay for cover.
BLD13-00084 FIRE-Final Inspection1/22/20131/23/20131/23/2013 12:27:44 PMAFAIL
See items number 3 and 4 on the general requirements page of the permit documents. Post a fire extinguisher as discussed and provide covers at the open electrical junction boxes.
FIR12-00086 INSP-Final Inspection1/11/20131/23/20131/23/2013 12:25:21 PMAPASS
Scope of fire alarm work passed site inspection. Permit finaled.
FIR12-00743 INSP-Final Inspection1/22/20131/23/20131/23/2013 12:23:51 PMAPASS
Fire sprinkler permit finaled.