Inspections for the day of: Thursday, January 23, 2014.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00300 ELE-Aging Inspection1/23/20141/23/20141/23/2014 4:51:20 PM DONE
Still under construction
ELE13-03579 Rough-In Permanent Service1/23/20141/23/20141/23/2014 4:44:24 PMPFAIL
334.30- NM cable shall be supported at intervals not to exceed 4 1/2', NM cable shall be secured within 12" of boxes. lower stair cans, stair light, garage.
314.17- NM sheathing shall enter box minimum of 1/4". J-box by garage door
ELE14-00116 Final1/23/20141/23/20141/23/2014 4:23:13 PMPNH
Phone #: ###-#### >> Inspection requested via web by Dan Rohl No one available for access
ELE13-03031 Final1/23/20141/23/20141/23/2014 3:28:36 PMPPASS
Contact: Wes Powell Phone #: ###-#### >> Inspection requested via web by Deb Gooden Final ok
ELE13-02057 Electrical Rough-In1/23/20141/23/20141/23/2014 2:43:31 PMPFAIL
3rd Floor corridor. Levi on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen Corrections not complete. 300.11- Ceiling support system supported by wires so all recessed cans and light boxes shall be supported independant of ceiling support system
GCE14-00014 GCE-Rough-In1/23/20141/23/20141/23/2014 1:45:44 PMPPASS
David ###-#### Rough in ok cover
GCE14-00014 GCE-Permanent Service1/23/20141/23/20141/23/2014 1:44:55 PMPPASS
David ###-#### p/s u/g n ok
ELE14-00188 Electrical Rough-In1/22/20141/23/20141/23/2014 1:17:08 PMPPASS
Phone #: ###-#### >> Inspection requested via web by David Nelson Rough in ok cover
ELE13-03443 Final1/23/20141/23/20141/23/2014 12:55:51 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Final ok
ELE13-02867 Final1/23/20141/23/20141/23/2014 12:39:54 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Mike Basye Final ok
ELE13-03484 Electrical Rough-In1/22/20141/23/20141/23/2014 12:28:20 PMAPASS
Please inspect ceiling grid area. Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS Ceiling rough in ok cover
ELE14-00162 Permanent Service1/23/20141/23/20141/23/2014 10:33:01 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Patrick Paz p/s o/h rec ok
ELE14-00185 Conference1/22/20141/23/20141/23/2014 10:16:38 AMADONE
Would like to discuss the service layout Phone #: ###-#### >> Inspection requested via web by Brad Baker Discussed Service location, overhead service entrance clearance, additional service on building feeds under ground to boise weekly, Flat work space in front of CT can
ELE13-03458 Final1/22/20141/23/20141/23/2014 9:45:01 AMAPASS
corrections made ready for a final
Phone #: ###-#### >> Inspection requested via web by Don Lustig Final ok
ELE13-02469 Electrical Rough-In1/23/20141/23/20141/23/2014 9:31:05 AMAPASS
Contact: Jeremy Thornock Phone #: ###-#### >> Inspection requested via web by Deb Gooden All ceiling rough in ok cover
ELE13-02783 Electrical Rough-In1/23/20141/23/20141/23/2014 9:30:08 AMAPASS
Contact: Jeremy Thornock Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inner offices ceiling rough in ok cover
ELE13-02787 Electrical Rough-In1/22/20141/23/20141/23/2014 9:29:14 AMAPASS
Contact: Wes Powell... ceiling and wall inspection please Phone #: ###-#### >> Inspection requested via web by DebGooden Pocket wall and 2 medium conference room ceilings rough in ok cover
ELE13-02654 Final1/22/20141/23/20141/23/2014 9:27:23 AMAPASS
Danny on site. Corrections noted have been fixed. Phone #: ###-#### >> Inspection requested via web by Buster Bowen Final ok
ELE13-02501 Final1/22/20141/23/20141/22/2014 2:47:21 PMAPASS
Please contact Brian for access Phone #: ###-#### >> Inspection requested via web by Tina Payne Service for pre fab building. Final ok