ELE11-00300
| ELE-Aging Inspection | 1/23/2014 | 1/23/2014 | 1/23/2014 4:51:20 PM | | DONE |
|
|
Still under construction
|
ELE13-03579
| Rough-In Permanent Service | 1/23/2014 | 1/23/2014 | 1/23/2014 4:44:24 PM | P | FAIL |
|
|
334.30- NM cable shall be supported at intervals not to exceed 4 1/2', NM cable shall be secured within 12" of boxes. lower stair cans, stair light, garage. 314.17- NM sheathing shall enter box minimum of 1/4". J-box by garage door
|
ELE14-00116
| Final | 1/23/2014 | 1/23/2014 | 1/23/2014 4:23:13 PM | P | NH |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl No one available for access
|
ELE13-03031
| Final | 1/23/2014 | 1/23/2014 | 1/23/2014 3:28:36 PM | P | PASS |
|
|
Contact: Wes Powell Phone #: ###-#### >> Inspection requested via web by Deb Gooden Final ok
|
ELE13-02057
| Electrical Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 2:43:31 PM | P | FAIL |
|
|
3rd Floor corridor. Levi on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen Corrections not complete. 300.11- Ceiling support system supported by wires so all recessed cans and light boxes shall be supported independant of ceiling support system
|
GCE14-00014
| GCE-Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 1:45:44 PM | P | PASS |
|
|
David ###-#### Rough in ok cover
|
GCE14-00014
| GCE-Permanent Service | 1/23/2014 | 1/23/2014 | 1/23/2014 1:44:55 PM | P | PASS |
|
|
David ###-#### p/s u/g n ok
|
ELE14-00188
| Electrical Rough-In | 1/22/2014 | 1/23/2014 | 1/23/2014 1:17:08 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson Rough in ok cover
|
ELE13-03443
| Final | 1/23/2014 | 1/23/2014 | 1/23/2014 12:55:51 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Final ok
|
ELE13-02867
| Final | 1/23/2014 | 1/23/2014 | 1/23/2014 12:39:54 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Mike Basye Final ok
|
ELE13-03484
| Electrical Rough-In | 1/22/2014 | 1/23/2014 | 1/23/2014 12:28:20 PM | A | PASS |
|
|
Please inspect ceiling grid area. Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS Ceiling rough in ok cover
|
ELE14-00162
| Permanent Service | 1/23/2014 | 1/23/2014 | 1/23/2014 10:33:01 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Patrick Paz p/s o/h rec ok
|
ELE14-00185
| Conference | 1/22/2014 | 1/23/2014 | 1/23/2014 10:16:38 AM | A | DONE |
|
|
Would like to discuss the service layout Phone #: ###-#### >> Inspection requested via web by Brad Baker Discussed Service location, overhead service entrance clearance, additional service on building feeds under ground to boise weekly, Flat work space in front of CT can
|
ELE13-03458
| Final | 1/22/2014 | 1/23/2014 | 1/23/2014 9:45:01 AM | A | PASS |
|
|
corrections made ready for a final Phone #: ###-#### >> Inspection requested via web by Don Lustig Final ok
|
ELE13-02469
| Electrical Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 9:31:05 AM | A | PASS |
|
|
Contact: Jeremy Thornock Phone #: ###-#### >> Inspection requested via web by Deb Gooden All ceiling rough in ok cover
|
ELE13-02783
| Electrical Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 9:30:08 AM | A | PASS |
|
|
Contact: Jeremy Thornock Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inner offices ceiling rough in ok cover
|
ELE13-02787
| Electrical Rough-In | 1/22/2014 | 1/23/2014 | 1/23/2014 9:29:14 AM | A | PASS |
|
|
Contact: Wes Powell... ceiling and wall inspection please Phone #: ###-#### >> Inspection requested via web by DebGooden Pocket wall and 2 medium conference room ceilings rough in ok cover
|
ELE13-02654
| Final | 1/22/2014 | 1/23/2014 | 1/23/2014 9:27:23 AM | A | PASS |
|
|
Danny on site. Corrections noted have been fixed. Phone #: ###-#### >> Inspection requested via web by Buster Bowen Final ok
|
ELE13-02501
| Final | 1/22/2014 | 1/23/2014 | 1/22/2014 2:47:21 PM | A | PASS |
|
|
Please contact Brian for access Phone #: ###-#### >> Inspection requested via web by Tina Payne Service for pre fab building. Final ok
|