ELE13-03374
| Final | 1/23/2014 | 1/23/2014 | 1/23/2014 3:48:25 PM | P | PART |
|
|
KEVIN - PARTIAL Phone #: ###-#### Partial final tell the non listed panels are replaced with listed and labeled panels. Two week grace period.
|
ELE13-03402
| Electrical Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 3:37:21 PM | P | PASS |
|
|
AARON Phone #: ###-#### rough-in ok cover new bathroom in garage
|
ELE14-00138
| Temporary Service | 1/23/2014 | 1/23/2014 | 1/23/2014 2:31:36 PM | P | FAIL |
|
|
Temporary overhead power pole for job site. Phone #: ###-#### >> Inspection requested via web by Spencer McLean Power already connected prior to service inspection. NEC 400.5 Table 400.5(A) Column A #6 SOOW cord ampacity 45 ampere on 60 amp breaker. Secure cable to temp. pole were no strain relief connector is used.
|
ELE14-00166
| Electrical Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 1:43:03 PM | P | PASS |
|
|
lighting retro rough in. Working in back warehouse today. Phone #: ###-#### >> Inspection requested via web by Tim Dunlop UL listed kits rough-in ok
|
ELE13-02911
| Final | 1/23/2014 | 1/23/2014 | 1/23/2014 1:26:55 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Louis Keller UL LIsted menu signs, final ok
|
ELE13-03489
| Final | 1/22/2014 | 1/23/2014 | 1/23/2014 1:05:50 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack final ok no C of O card on site
|
ELE13-03065
| Final | 1/22/2014 | 1/23/2014 | 1/23/2014 12:50:54 PM | A | FAIL |
|
|
garage code 6829 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey East garage receptacle, front outside receptacle and rear patio receptacle all have no power
|
ELE14-00168
| Permanent Service | 1/22/2014 | 1/23/2014 | 1/23/2014 12:19:12 PM | A | PASS |
|
|
power off over a year, need inspection on service to get power on. Any questions call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose p/s u/g rec ok NEC 250.56 before final inspection
|
ELE14-00158
| Electrical Rough-In | 1/22/2014 | 1/23/2014 | 1/23/2014 11:55:03 AM | A | PASS |
|
|
UFER ground inspection, Geoff Hannaford is contact ###-####. Phone #: ###-#### >> Inspection requested via web by Debby Pierce r/i ok cover concrete encased electrode
|
ELE14-00180
| Rough-In Permanent Service | 1/22/2014 | 1/23/2014 | 1/23/2014 10:04:30 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe NEC 240.83 Interrupting rating of main breaker
|
ELE14-00180
| Electrical Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 10:02:33 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe rough-in ok cover No permanent service without available AFC
|
ELE12-00713
| Final | 1/22/2014 | 1/23/2014 | 1/23/2014 9:22:46 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Lori Stout job complete, final ok
|
ELE14-00163
| Electrical Rough-In | 1/22/2014 | 1/23/2014 | 1/23/2014 8:52:37 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Cindie Swaim corrections done, rough-in ok cover No electrical conduit to dettached structure on this inspection
|
ELE12-01575
| ELE-Aging Inspection | 1/23/2014 | 1/23/2014 | 1/23/2014 8:27:45 AM | | DONE |
|
|
see final
|
ELE12-01575
| Final | 1/23/2014 | 1/23/2014 | 1/23/2014 8:27:12 AM | A | PASS |
|
|
UL listed signs final ok
|