Inspections for the day of: Monday, January 23, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00160 Permanent Service1/23/20171/23/20171/23/2017 2:04:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley
Contractor not sure if remodel work needed. Will check after house clean up complete.
p/s o/h rec ok
ELE17-00156 Conference1/23/20171/23/20171/23/2017 1:55:03 PMPDONE
Please contact Todd Sellman to meet onsite for conference. ###-####. Phone #: ###-#### Inspection requested via web by Todd Sellman
Contactor to add new 480 volt service to building. CT meter at outdoor transformer. Main disconnecting means outside on south side. Once on inside plans are to install a gutter to tap off and refeed existing disconnects.
Issues
BCC 4-05-32- Code violations not to be retained.
110.26(A)- Minimum work space shall be provided for all disconnecting means. 36" deep and 30" wide.
110.26(B)- Work space shall be clear of foriegn equipment, compressor encroaches on space.
404.8(A)- Max height of disconnecting means shall not exceed 6'7".
ELE16-03550 Final1/23/20171/23/20171/23/2017 12:51:53 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Final ok
ELE15-01348 Final1/20/20171/23/20171/23/2017 10:46:07 AMAPART
Please call Tom Hartung for TCO inspection of levels 7,8,9 of the office building. Phone #: ###-#### Inspection requested via web by Tom Betty
Level 7 board room 749-2 circuit 72-B to be locked off until table is installed. MC thru floor can not be romoved without removing drywall. All levels furniture covers some are loose on line volt and low volt sides. Some card reader low volt boxes open. Shunt trip locations not changed as per State inspectors request, general contractor hoping for variance.
Signed TCO on HQ.
ELE16-01838 Final1/20/20171/23/20171/23/2017 10:45:35 AMAPART
Please call Tom Hartung for TCO inspection on levels 7,8,9 of the office building. Phone #: ###-#### Inspection requested via web by Tom Betty
Level 7 board room 749-2 circuit 72-B to be locked off until table is installed. MC thru floor can not be romoved without removing drywall. All levels furniture covers some are loose on line volt and low volt sides. Some card reader low volt boxes open. Shunt trip locations not changed as per State inspectors request, general contractor hoping for variance.
Signed TCO on HQ.