Inspections for the day of: Monday, January 23, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00143 Rough-In Permanent Service1/20/20171/23/20171/23/2017 2:05:46 PMPPASS
Phone #: ###-#### Inspection requested via web by Krista Ratterree
rough-in ok cover p/s u/g n ok(could not place p/s sticker on meter due to 14" of water in front)
ELE17-00143 Electrical Rough-In1/20/20171/23/20171/23/2017 2:03:37 PMPPASS
Phone #: ###-#### Inspection requested via web by Krista Ratterree
Rough-in ok cover(duplicate inspection request)
ELE16-03541 Final1/23/20171/23/20171/23/2017 1:50:30 PMPPASS
The Corrections Have Been Made This Morning And We Are Ready To Go The Lock box Is 8483. Thanks Dave Call With Any Questions Or Concerns! Phone #: ###-#### Inspection requested via web by jason shifflett
Corrections fixed final ok
ELE16-02816 Final1/23/20171/23/20171/23/2017 1:21:00 PMPFAIL
3- outlets south wall in basement (exercise equipment) No stairs built in garage. Builder was supposed to leave ladder on site. Phone #: ###-#### Inspection requested via web by Greg Traudt
406.6 Faceplates required(tv outlet combo in bonus over garage)
334.12(b)(4) Type NM cable shall not be used in a wet location(a/c's)
ELE17-00037 Electrical Rough-In1/20/20171/23/20171/23/2017 11:09:04 AMAPASS
Rough-In Wall Inspection Building 2
Contact Cesar Salcedo
###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek
Issue with paddel fan without boxes and non compliant wiring with be resolved with proper methods. Building 2 addition for micro ok cover
ELE17-00135 Conference1/19/20171/23/20171/23/2017 10:44:44 AMADONE
Greg Critchfield is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Discussed wiring methods for for replacement of fire pump controll and transfer switch and bringing it to code with listed fire control panels. Will receive the proper one line diagram once engineer has sent it to EC and will review once it's recieved.