BLD15-03423
| FIRE-Final Inspection | 1/22/2018 | 1/23/2018 | 1/23/2018 2:58:34 PM | A | CANC |
|
|
Issues with fire alarm on level 6, more testing needs to be completed before TCO, this request is cancelled.
|
BLD15-03835
| FIRE-Final Inspection | 1/22/2018 | 1/23/2018 | 1/23/2018 2:58:17 PM | A | CANC |
|
|
Issues with fire alarm on level 6, more testing needs to be completed before TCO, this request is cancelled.
|
FIR16-00383
| INSP-Alarm Testing | 1/23/2018 | 1/23/2018 | 1/23/2018 2:57:28 PM | P | DONE |
|
|
More fire alarm testing needs to happen on level 6 before TCO
|
FIR17-00173
| INSP-Final Inspection | 1/23/2018 | 1/23/2018 | 1/23/2018 1:52:25 PM | P | PART |
|
|
Partial final inspection complete for overhead fire sprinklers. Irrigation needs to isolate when flow switch activates, permit cannot be finaled until irrigation isolation on flow switch activation is verified.
|
FIR18-00041
| INSP-Final Inspection | 1/22/2018 | 1/23/2018 | 1/23/2018 11:52:58 AM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
BLD17-03990
| FIRE-Final Inspection | 1/22/2018 | 1/23/2018 | 1/23/2018 10:41:58 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher will be mounted in discussed location. Final life fire safety inspection complete.
|
FIR17-00761
| INSP-Final Inspection | 1/23/2018 | 1/23/2018 | 1/23/2018 10:40:58 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
FIR17-00737
| INSP-Final Inspection | 1/22/2018 | 1/23/2018 | 1/23/2018 10:40:28 AM | A | PASS |
|
|
Final fire alarm nispection for area of work complete.
|
FIR18-00033
| INSP-Sprinkler Rough-in | 1/22/2018 | 1/23/2018 | 1/23/2018 10:04:34 AM | A | PASS |
|
|
Rough to cover inspection for area of work complete, approved for cover.
|