ELE19-00276
| Temporary Service | 1/23/2019 | 1/23/2019 | 1/23/2019 2:26:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE19-00156
| Final | 1/22/2019 | 1/23/2019 | 1/23/2019 2:26:39 PM | A | NH |
|
|
Tony Phone #: ###-#### No one home
|
ELE18-04217
| Final | 1/22/2019 | 1/23/2019 | 1/23/2019 9:44:45 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 210.52 All basins shall have a receptacle located within 36" 210.52 Wall spacing shall be 6' from a cabinet in kitchen, counter receptacles do not count for wall spacing 406 tamper resistant in pantry
|
ELE16-03912
| ELE-Request for Extension | 1/22/2019 | 1/23/2019 | 1/23/2019 12:00:00 AM | A | CANC |
|
|
JOshua Phone #: ###-####
|