FIR18-00873
| INSP-Alarm Testing | 1/21/2019 | 1/23/2019 | 1/23/2019 2:13:13 PM | P | PART |
|
|
Fire sprinkler monitoring has been verified, need to have bell relocated to be above the FDC. Provide knox box as shown in the fire alarm review comments.
Coordinating with Phoenix Fire to accomplish sprinkler inspection at same time. Phone #: ###-#### Inspection requested via web by Jack Schmidt
|
FIR18-00298
| INSP-Final Inspection | 1/21/2019 | 1/23/2019 | 1/23/2019 2:11:55 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Contact Leroy Anderson ###-#### 30 Min prior to Fire Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD18-03851
| FIRE-Final Inspection | 1/23/2019 | 1/23/2019 | 1/23/2019 1:58:44 PM | P | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire xtinguisher will be mounted in discussed location. Final life fire safety inspection for area of work complete.
Please call 30 minutes in advance so I can meet you on site. Thanks. Phone #: ###-#### Inspection requested via web by Don Walker
|
FIR18-00831
| INSP-Final Inspection | 1/23/2019 | 1/23/2019 | 1/23/2019 1:54:05 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
FIR18-00827
| INSP-Sprinkler Rough-in | 1/23/2019 | 1/23/2019 | 1/23/2019 11:40:37 AM | P | FAIL |
|
|
As stated before, piping cannot be covered before rough to cover inspection, all cover material preventing inspection for overehad fire sprinklers needs to be removed. Tenting on level 3 needs to be repaired before cover can be approved.
Gerarrdo is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-04256
| BLD-Aging Inspection | 1/23/2019 | 1/23/2019 | 1/23/2019 11:33:57 AM | | DEFR |
|
|
475 tco needs follow up.
|
FIR18-00814
| INSP-Final Inspection | 1/22/2019 | 1/23/2019 | 1/23/2019 11:14:05 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00814
| INSP-Sprinkler Rough-in | 1/23/2019 | 1/23/2019 | 1/23/2019 11:13:53 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping and tenting (all tenting in place at time of inspection) complete, approved for cover.
|
FIR19-00014
| INSP-Final Inspection | 1/22/2019 | 1/23/2019 | 1/23/2019 10:40:50 AM | A | PASS |
|
|
Final inspection for hood suppression system complete.
Richard Phone #: ###-####
|
BLD17-04482
| FIRE-Final Inspection | 1/22/2019 | 1/23/2019 | 1/23/2019 9:54:21 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Darius Saxton
|
BLD18-01779
| FIRE-Final Inspection | 1/22/2019 | 1/23/2019 | 1/23/2019 9:54:04 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Darius Saxton
|
FIR18-00792
| INSP-Final Inspection | 1/22/2019 | 1/23/2019 | 1/23/2019 9:53:23 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
FIR18-00258
| INSP-Final Inspection | 1/22/2019 | 1/23/2019 | 1/23/2019 9:52:59 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Brian Phone #: ###-####
|
FIR18-00759
| INSP-Final Inspection | 1/22/2019 | 1/23/2019 | 1/23/2019 9:52:28 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Rick-fire life safety to be done at the same time Phone #: ###-####
|
FIR19-00010
| INSP-Final Inspection | 1/21/2019 | 1/23/2019 | 1/23/2019 9:16:29 AM | A | FAIL |
|
|
Power to little fryer on left did not isolate when suppression system was tripped, all energy needs to be isolated with hood activation. Hood has excessive build up of grease behind filoters, hood needs cleaned before next inspection.
I''m trying to do this final early in the morning, so they can still open up for regular business hours. Thank you! Phone #: ###-#### Inspection requested via web by Don Kartchner
|
BLD19-00149
| FIRE-Final Inspection | 1/18/2019 | 1/23/2019 | 1/23/2019 8:06:07 AM | A | FAIL |
|
|
Space was not open at time inspection could be completed, inspection will need to be rescheduled.
Brian Phone #: ###-####
|
BLD18-04086
| FIRE-Final Inspection | 1/23/2019 | 1/23/2019 | 1/23/2019 7:32:39 AM | A | PASS |
|
|
Fire alarm inspection has been finaled, final life fire safety inspection for area of work complete.
|
FIR19-00003
| INSP-Final Inspection | 1/18/2019 | 1/23/2019 | 1/23/2019 7:31:10 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Ken Webster
|