Inspections for the day of: Wednesday, January 23, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00053 Rough-in1/23/20191/23/20191/23/2019 4:00:05 PMPPART
Inspection requested via web by Konrad Swartz
- Man J needs to be stamped by the city and onsite
- range hood vent needs to be smooth walled pipe
- dryer vent needs to be installed for common laundry room and needs a backdraft damper

MEC19-00050 Rough-in1/23/20191/23/20191/23/2019 3:48:36 PMPPART
Inspection requested via web by Konrad Swartz
- Man J needs to be stamped by the city and onsite
- range hood vent needs to be smooth walled pipe
- one dryer vent needs new back draft damper installed
- one unit has line set insulation that needs fixed
MEC18-06138 Pressure Test1/17/20191/23/20191/23/2019 2:59:41 PMPPASS
Please call our technician when on way so he can meet you onsite for the flue pressure test: Eric ###-####. Also please call the customer when on way so he can meet you onsite: Chad ###-####. Phone #: ###-####
Inspection requested via web by Arielle
Hendricks
- 5lb flue test ok co ok
final ok
MEC18-04840 Final1/23/20191/23/20191/23/2019 2:25:25 PMPFAIL
Call 2089064067 when you arrive so we can tell you how to find the key to access the house. Home is vacant. Phone #: ###-#### Inspection requested via web by Les Gargan
- gas line at furnace needs a sediment trap after shut off valve
-secondary drain needs a wet switch installed. it cant be ran into the pump for the primary drain
- A/C needs 20 amp fuses installed at service disconnect
- I also noticed a new gas fireplace was installed and vented most likely by another contractor which wasnt permited. fireplace installers need to pull a permit before this mech permit can be finaled
MEC19-00213 Rough-in1/22/20191/23/20191/23/2019 1:56:23 PMPPASS
Call jason wtih any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
- R/I ok
- 2x 5lb flue test ok
-20lb gas pressure test ok
MEC18-05047 Final1/23/20191/23/20191/23/2019 1:30:05 PMPPART
Please call Russ, Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- need to see guardrails installed at roof access
MEC19-00304 Final1/22/20191/23/20191/23/2019 1:11:34 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace ac coil co ok
MEC19-00287 Final1/21/20191/23/20191/23/2019 12:52:14 PMPPASS
My apologies on this one! Requests inspection only from 12 -1 and a call about 15 minutes prior to inspection. Bhumika Chhabra. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- A/C final co ok
MEC18-06065 Final1/18/20191/23/20191/23/2019 11:46:25 AMAPASS
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 11:30 . Contact for Right Now is Mary ###-####
Phone #: ###-#### Inspection requested via web
by Mary LaFayette
- this install didnt need a 5lb flue pressure test witness performed 1- 90% furnace was in the garage and 1- 80% furnace inside the house
- 2 furnaces ac coil co ok
MEC18-05263 Final1/22/20191/23/20191/23/2019 10:15:37 AMAPASS
Please call when you are on your way so we can notify the customer. Thank you. Phone #: ###-#### Inspection requested via web by Dan McFate
- furnace only co ok
MEC19-00149 Final1/23/20191/23/20191/23/2019 9:39:14 AMAPASS
5lb flue test ok
- final ok
MEC18-05105 Final1/23/20191/23/20191/23/2019 9:17:32 AMAPASS
andy is contact Phone #: ###-#### Inspection requested via web by Aaron Alandt
- final ok
MEC17-04523 Final1/22/20191/23/20191/23/2019 9:17:08 AMAPASS
Daniel Sprague Phone #: ###-#### Inspection requested via web by Sheldon Lebow
- fireplace final ok
MEC18-06136 Pressure Test1/22/20191/23/20191/23/2019 8:43:35 AMACANC
Phone #: ###-#### Inspection requested via web by Gary Reeves
- 5lb flue pressure test fail guage was under 5lb Inspection cancelled from web by: Gary Reeves
MEC18-06136 Rough-in1/22/20191/23/20191/23/2019 8:38:01 AMAPART
Phone #: ###-#### Inspection requested via web by Gary Reeves
- R/I ok but 5lb flue pressure test fail gauge was under 5lb
MEC17-04823 Mec-Aging Inspection1/23/20191/23/20191/23/2019 8:07:52 AM FAIL
scheduled inspection with homeowner
MEC17-05204 Mec-Aging Inspection1/23/20191/23/20191/23/2019 8:07:30 AM FAIL
MEC16-05348 Mec-Request for Extension1/22/20191/23/20191/23/2019 12:00:00 AMACANC
Joshua Phone #: ###-####