FIR19-00890
| INSP-Sprinkler Rough-in | 1/23/2020 | 1/23/2020 | 1/24/2020 7:55:54 AM | P | FAIL |
|
|
See the city approved plans for locations for corrections. Also the small room rule can not be used where the pendant heads have been calculated for 14x14 max spacingl.
Richard Clark is the contact for this RTC inspection. He needs 45 min notice before appointment as he will be at another job site. Thank you for your help. Have a great day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00661
| INSP-Sprinkler Rough-in | 1/22/2020 | 1/23/2020 | 1/24/2020 6:20:15 AM | P | CANC |
|
|
Cover Inspection, Jim will attend Phone #: ###-#### Inspection requested via web by Connie Danes
|
BLD19-04769
| FIRE-Final Inspection | 1/22/2020 | 1/23/2020 | 1/23/2020 1:13:26 PM | A | FAIL |
|
|
Fire alarm panel needs to be cleaned up, fire sprinkler permit needed for modifications, new door hardware to be single action type, repair exit signs and emergency lights.
Ben Phone #: ###-####
|
BLD19-04869
| FIRE-Final Inspection | 1/22/2020 | 1/23/2020 | 1/23/2020 1:12:17 PM | A | FAIL |
|
|
Fire alarm panel needs to be cleaned up, fire sprinkler permit needed for modifications, new door hardware to be single action type, repair exit signs and emergency lights.
Ben Phone #: ###-####
|
BLD20-00120
| FIRE-Final Inspection | 1/22/2020 | 1/23/2020 | 1/23/2020 1:05:39 PM | A | FAIL |
|
|
Revised floor plan needed. All other life safety items appear ok.
David Phone #: ###-####
|
FIR19-00774
| INSP-Sprinkler Rough-in/Hydro | 1/22/2020 | 1/23/2020 | 1/23/2020 10:55:12 AM | A | PASS |
|
|
Underground hydro supply line witnessed on building B. underground // Bill Phone #: ###-####
|
FIR19-00468
| INSP-Sprinkler Rough-in/Hydro | 1/22/2020 | 1/23/2020 | 1/23/2020 10:51:56 AM | A | PASS |
|
|
2nd floor rough in pass. Verify baffles are installed on 2nd floor.
RUDY IS OUR CONTACT. THIS IS A ROUGH-IN FOR THE 2ND FLOOR Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
BLD20-00207
| FIRE-Final Inspection | 1/22/2020 | 1/23/2020 | 1/23/2020 10:47:03 AM | A | FAIL |
|
|
Floor plan does not match building. Inspection will need to be rescheduled after correct floor plan is provided. Owner was advised to submit correct floor plan and resubmit. Emergency light in dining area not working. Additional exit lighting may be required with revised floor plan submittal.
Susana Phone #: ###-####
|
FIR19-00937
| INSP-Final Inspection | 1/20/2020 | 1/23/2020 | 1/23/2020 9:23:39 AM | A | PASS |
|
|
Permit finaled.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00955
| INSP-Final Inspection | 1/20/2020 | 1/23/2020 | 1/23/2020 9:22:52 AM | A | FAIL |
|
|
Plan mods are needed to show the 30cd strobe. Need city approved plans on site as well.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00955
| INSP-Final Inspection | 1/17/2020 | 1/23/2020 | 1/20/2020 12:24:10 PM | A | CANC |
|
|
Needs to be done at 7:30am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
FIR19-00937
| INSP-Final Inspection | 1/17/2020 | 1/23/2020 | 1/20/2020 12:22:39 PM | A | CANC |
|
|
Needs to be done at 7:30 am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|