ELE02-00186
| Permanent Service | 1/23/2002 | 1/24/2002 | 1/24/2002 12:00:00 AM | A | FAIL |
|
|
###-####- derrick cor. posted called 250-52 (a) (1) grd to water 1st 5 ft needs 4 wire to range and dryer from sub panel, and install guy kit after new shingles are installed 1/24/2002 11:09:35 AM
|
ELE02-00189
| Electrical Rough-In | 1/23/2002 | 1/24/2002 | 1/24/2002 12:00:00 AM | A | PASS |
|
|
###-#### ok 1/24/2002 11:59:27 AM
|
ELE01-03334
| Final | 1/23/2002 | 1/24/2002 | 1/24/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 01/23/2002 at 15:55:39. Contact: ###-####. correction 410-14 (b) need to punch k o in fixture for access to box talked with contractor at job site 1/24/2002 10:27:25 AM
|
ELE02-00200
| Final | 1/24/2002 | 1/24/2002 | 1/24/2002 12:00:00 AM | P | PASS |
|
|
this permit is for the fuel canopy, the other elect. permit is for the store lh ok 1/24/2002 3:38:13 PM
|