BLD01-02967
| FIRE-Final Inspection | 1/23/2003 | 1/24/2003 | 1/24/2003 12:00:00 AM | A | FAIL |
|
|
Phone #: ###-#### Provide signage on the fire riser door and provide Knox Box 1/24/2003 9:55:45 AM
|
FIR02-00162
| INSP-Final Inspection | 1/24/2003 | 1/24/2003 | 1/24/2003 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled
|
FIR02-00325
| INSP-Final Inspection | 1/21/2003 | 1/24/2003 | 1/24/2003 12:00:00 AM | P | FAIL |
|
|
###-#### matt The south in-duct smoke detector did not operate and needs to be tested. Provide map at the FACP. Verify dedicated circuit location 1/24/2003 3:59:07 PM
|
FIR02-00256
| INSP-Final Inspection | 1/23/2003 | 1/24/2003 | 1/24/2003 12:00:00 AM | P | FAIL |
|
|
all spot smoke detectors and pull stations have been tested. The zone labeling for the smokes and the pull stations that are shown on the plans is incorrect and needs to be shown correctly on the as-built plans. No duct smoke detectors have been tested. One of the duct detectors in the south end of the building is installed correctly. All audio/visual devices were tested and functioned correctly. Smokes, pulls and A/V's are installed in the correct locations. No other devices have been tested including the NAC panels, FACP panel or fire sprinkler system devices. Review notes have not been looked at by me. 1/24/2003 3:57:34 PM
|