FIR04-00529
| FIR-Aging Inspection | 1/24/2005 | 1/24/2005 | 1/24/2005 12:00:00 AM | | NR |
|
|
work in progress 1/24/2005 1:13:09 PM
|
FIR04-00574
| INSP-Final Inspection | 1/21/2005 | 1/24/2005 | 1/24/2005 12:00:00 AM | A | FAIL |
|
|
Rename the PIV and Duct Detector from zones to actual text so that it is consistant with the other devices. Signals that the monitoring station received do not match what was sent. Provide Knox Box and signage on the riser/fire alarm panel room door per review notes. Provide record of completion at final. 1/24/2005 11:29:35 AM
|
BLD04-01743
| FIRE-Final Inspection | 1/24/2005 | 1/24/2005 | 1/24/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 1/24/2005 12:53:34 PM
|