FIR11-00371
| INSP-Sprinkler Rough-in | 1/24/2012 | 1/24/2012 | 1/25/2012 10:33:10 AM | P | FAIL |
|
|
Additional upright sprinkler coverage is required due to a full height wall.
|
FIR11-00674
| INSP-Sprinkler Rough-in | 1/24/2012 | 1/24/2012 | 1/24/2012 3:10:42 PM | P | PASS |
|
|
ok to cover
|
FIR12-00016
| INSP-Sprinkler Rough-in | 1/24/2012 | 1/24/2012 | 1/24/2012 3:09:14 PM | P | PASS |
|
|
Piping above the hard lids is ok to cover. The new uprights around the full height wall are also complete.
|
BLD12-00012
| FIRE-Conference | 1/24/2012 | 1/24/2012 | 1/24/2012 2:03:39 PM | P | DONE |
|
|
Darren and I spoke about the two doors that will not arrive prior to the building being occupied. I was ok with verifying their install and hardware when a building final was requested at the same time the duct smoke detectors were addressed.
|
FIR11-00479
| INSP-Sprinkler Rough-in/Hydro | 1/24/2012 | 1/24/2012 | 1/24/2012 1:56:49 PM | P | PASS |
|
|
The hydro test at the riser passed.
|
FIR11-00674
| INSP-Sprinkler Rough-in | 1/24/2012 | 1/24/2012 | 1/24/2012 11:59:11 AM | P | FAIL |
|
|
Need to provide retaining straps and correct hanger attachment to the deck for the pendant in the closet. Currently the all thread rod has been bent on this hanger. Re-inspection has been scheduled for this afternoon.
|
FIR11-00479
| INSP-Sprinkler Rough-in/Hydro | 1/23/2012 | 1/24/2012 | 1/24/2012 11:50:31 AM | A | PART |
|
|
The hydro test for the system at the new lobby passed. The hydro test for the system at the new riser failed possibly due to the door to the riser room being left open. This test is rescheduled for this afternoon.
|
FIR11-00215
| INSP-Final Inspection | 1/23/2012 | 1/24/2012 | 1/24/2012 11:29:18 AM | A | CANC |
|
|
Canceled per phone conversation with Alex Phone #: ###-####
|