FIR12-00736
| INSP-Final Inspection | 1/23/2013 | 1/24/2013 | 1/24/2013 3:57:45 PM | P | CANC |
|
|
Canceled. Robert Gobler could not make it there when I could due to a previous engagment. He will reschedule
|
FIR12-00428
| INSP-Final Inspection | 1/24/2013 | 1/24/2013 | 1/24/2013 3:53:40 PM | P | CANC |
|
|
Canceled due to time constraints. Per agreement inspection is rescheduled for tomorrow morning at 7:30am. Also per tim he has not installed duct smoke detectors in some units that are missing. I asked him to bring as-built drawings showing the deleted devices. And that in the future if the devices are installed an additional permit will be required. The only other option is to install all devices. Tim Phone #: ###-####
|
FIR12-00591
| INSP-Final Inspection | 1/22/2013 | 1/24/2013 | 1/24/2013 3:49:49 PM | A | FAIL |
|
|
All Basement heat detectors are tested and passed. The Penthouse smoke detectors tested ok but the hvac units did not remain shut down under an alarm condition (which is required). All of the Main level smoke detectors were tested except for Engineering and the Studio. To finish project I need a print out of todays signals, hvac shutdown fixed, remaining Main Level areas tested, EOL verified as discussed, verify sync of audio/visual devices and as-builts with the correct floor layout (as of today it does not match).
|
FIR12-00075
| FIR-Aging Inspection | 1/24/2013 | 1/24/2013 | 1/24/2013 3:44:28 PM | | NR |
|
|
Per steve these DSC permits will all be scheduled shortly. Maps for the facp and other paperwork is being finished.
|
FIR12-00306
| FIR-Aging Inspection | 1/24/2013 | 1/24/2013 | 1/24/2013 3:43:04 PM | | NR |
|
|
Per steve these DSC permits will all be scheduled shortly. Maps for the facp and other paperwork is being finished.
|
FIR12-00638
| INSP-Final Inspection | 1/23/2013 | 1/24/2013 | 1/24/2013 1:10:39 PM | A | FAIL |
|
|
The outside alarm bell needs to be relocated to the front of the home. This was verified with Romeo. Once the bell has been retested the permit can be finaled.
|
FIR12-00638
| INSP-Supply line flush | 1/23/2013 | 1/24/2013 | 1/24/2013 11:22:06 AM | A | PASS |
|
|
Underground flush passed
|
FIR12-00691
| INSP-Sprinkler Rough-in | 1/23/2013 | 1/24/2013 | 1/24/2013 11:13:40 AM | A | PASS |
|
|
See the city approved plans for locations where the sprinkler piping can be covered. As-builts will be required to show the 3" main actual pipe routing
|
BLD12-02535
| FIRE-Final Inspection | 1/23/2013 | 1/24/2013 | 1/24/2013 10:34:38 AM | A | PASS |
|
|
Life safety passed. A racking permit is in the design process per the tenant owner.
|
BLD13-00087
| FIRE-Final Inspection | 1/23/2013 | 1/24/2013 | 1/24/2013 10:02:31 AM | A | FAIL |
|
|
Provide for annual inspection for the fire extinguisher, provide permanant sticker at the main exit and verify if additional permit is needed if you are going to connect the sink
|
BLD13-00094
| FIRE-Final Inspection | 1/23/2013 | 1/24/2013 | 1/24/2013 9:42:01 AM | A | FAIL |
|
|
See the city approved plans for corrections needed and their locations. They include doors that need to meet IFC 1008.1.4.4, repair exit signs and emergency lights, additional fire extinguisher and reversing hardware.
|