Inspections for the day of: Thursday, January 24, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00736 INSP-Final Inspection1/23/20131/24/20131/24/2013 3:57:45 PMPCANC
Canceled. Robert Gobler could not make it there when I could due to a previous engagment. He will reschedule
FIR12-00428 INSP-Final Inspection1/24/20131/24/20131/24/2013 3:53:40 PMPCANC
Canceled due to time constraints. Per agreement inspection is rescheduled for tomorrow morning at 7:30am. Also per tim he has not installed duct smoke detectors in some units that are missing. I asked him to bring as-built drawings showing the deleted devices. And that in the future if the devices are installed an additional permit will be required. The only other option is to install all devices. Tim Phone #: ###-####
FIR12-00591 INSP-Final Inspection1/22/20131/24/20131/24/2013 3:49:49 PMAFAIL
All Basement heat detectors are tested and passed. The Penthouse smoke detectors tested ok but the hvac units did not remain shut down under an alarm condition (which is required). All of the Main level smoke detectors were tested except for Engineering and the Studio. To finish project I need a print out of todays signals, hvac shutdown fixed, remaining Main Level areas tested, EOL verified as discussed, verify sync of audio/visual devices and as-builts with the correct floor layout (as of today it does not match).
FIR12-00075 FIR-Aging Inspection1/24/20131/24/20131/24/2013 3:44:28 PM NR
Per steve these DSC permits will all be scheduled shortly. Maps for the facp and other paperwork is being finished.
FIR12-00306 FIR-Aging Inspection1/24/20131/24/20131/24/2013 3:43:04 PM NR
Per steve these DSC permits will all be scheduled shortly. Maps for the facp and other paperwork is being finished.
FIR12-00638 INSP-Final Inspection1/23/20131/24/20131/24/2013 1:10:39 PMAFAIL
The outside alarm bell needs to be relocated to the front of the home. This was verified with Romeo. Once the bell has been retested the permit can be finaled.
FIR12-00638 INSP-Supply line flush1/23/20131/24/20131/24/2013 11:22:06 AMAPASS
Underground flush passed
FIR12-00691 INSP-Sprinkler Rough-in1/23/20131/24/20131/24/2013 11:13:40 AMAPASS
See the city approved plans for locations where the sprinkler piping can be covered. As-builts will be required to show the 3" main actual pipe routing
BLD12-02535 FIRE-Final Inspection1/23/20131/24/20131/24/2013 10:34:38 AMAPASS
Life safety passed. A racking permit is in the design process per the tenant owner.
BLD13-00087 FIRE-Final Inspection1/23/20131/24/20131/24/2013 10:02:31 AMAFAIL
Provide for annual inspection for the fire extinguisher, provide permanant sticker at the main exit and verify if additional permit is needed if you are going to connect the sink
BLD13-00094 FIRE-Final Inspection1/23/20131/24/20131/24/2013 9:42:01 AMAFAIL
See the city approved plans for corrections needed and their locations. They include doors that need to meet IFC 1008.1.4.4, repair exit signs and emergency lights, additional fire extinguisher and reversing hardware.