Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00157 Final1/23/20171/24/20171/24/2017 3:12:56 PMPPASS
Call half hour to meet // Sara Phone #: ###-####
Changed furnace from electric to gas. Final ok
ELE16-00805 Final1/24/20171/24/20171/24/2017 2:31:22 PMPNR
Please call Jared when you are on your way ###-####. Thank You!! Phone #: ###-#### Inspection requested via web by Clay Morgan
Front covered patio not complete.
3rd floor no work performed. Used for storage.
2nd floor master bed and bath remodel.
Main level kitchen and powder bath remodel.
basement/crawl equipment only in this space.
Changed plugs and switches thru out. Listing confirmed on push button switches.
Items to complete, install can trim in master closet with enclosed lamp as per 410.16. GFCI protect receptacle in laundry 2nd floor left of sink as per 210.8. Mantle in dining room is on hooks and removable so receptacle located behind ok.
Interior checked ok to occupy. Will recall when front patio complete.
ELE17-00167 Rough-In Permanent Service1/23/20171/24/20171/24/2017 1:14:28 PMPPASS
The later in the pm the better Phone #: ###-#### Inspection requested via web by Warren Fry
Garage behind house, office in west end of garage. Bath and storage rooms with new service on garage. Rough in ok cover
p/s o/h n ok
ELE17-00173 Temporary Service1/24/20171/24/20171/24/2017 12:36:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Paula Gratiot t/s o/h n ok
ELE16-03999 Final1/23/20171/24/20171/24/2017 11:18:56 AMAFAIL
Phone #: ###-#### Inspection requested via web by Chris Berthelot
330.12(1)- MC cable shall not be installed where subject to physical damage. Thru floor to wall receptacles.
314.25- All wiring in boxes shall have covers. Basement, abandoned wiring shall be pushed in ceilings or walls not exposed.
422.31(B)- Water heater shall have a disconnecting means. 110.25 lockout acceptable. Locking mechanism shall be part of switch or circuit breaker as per Daryl DeGrange.
ELE16-02430 Final1/23/20171/24/20171/24/2017 9:32:20 AMAPASS
House code: 2129
Call Kaden with any questions ###-#### Phone #: ###-#### Inspection requested via web by William Salts Final ok
ELE17-00125 Rough-In Permanent Service1/23/20171/24/20171/24/2017 8:51:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok