FIR19-00601
| INSP-Sprinkler Rough-in | 1/24/2020 | 1/24/2020 | 1/24/2020 3:01:27 PM | P | PASS |
|
|
Tenting inspection passed. Piping can be covered. Call Anthony when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00661
| INSP-Sprinkler Rough-in | 1/23/2020 | 1/24/2020 | 1/24/2020 1:21:38 PM | P | FAIL |
|
|
Need city approved plans that match the layout of the installed piping. Need through bolts for the earthquake attachments at the roof structure.
Rough in for Cover - Jim will attend Phone #: ###-#### Inspection requested via web by Connie Danes
|
BLD06-02322
| FIRE-Final Inspection | 1/23/2020 | 1/24/2020 | 1/24/2020 12:44:42 PM | A | PART |
|
|
Life safety is ok for a temp for Building A (north building). Lee Phone #: ###-####
|
BLD19-04769
| FIRE-Final Inspection | 1/23/2020 | 1/24/2020 | 1/24/2020 12:37:06 PM | A | FAIL |
|
|
Life safety will be ok to final when the fire sprinkler permit has been inspected/finaled.
Ben Phone #: ###-####
|
BLD19-04869
| FIRE-Final Inspection | 1/23/2020 | 1/24/2020 | 1/24/2020 12:36:41 PM | A | FAIL |
|
|
Life safety will be ok to final when the fire sprinkler permit has been inspected/finaled.
Ben Phone #: ###-####
|
FIR19-00702
| INSP-Sprinkler Rough-in | 1/24/2020 | 1/24/2020 | 1/24/2020 12:01:14 PM | P | PART |
|
|
FIrst floor inspection stopped due to pipe routing changes and additional fittings that need approved prior to a cover approval. The second floor rough-in passed and piping can be covered in the residence rooms. An additional cover inspection will be needed when the T-bar in the corridor has been installed and pendants cut to it.
First and second floors, overhead rough. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00304
| INSP-Final Inspection | 1/23/2020 | 1/24/2020 | 1/24/2020 8:52:29 AM | A | PASS |
|
|
Permit finaled. Sprinkler system had been turned off but is now active.
Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR19-00816
| INSP-Sprinkler Rough-in | 1/24/2020 | 1/24/2020 | 1/24/2020 7:52:52 AM | P | CANC |
|
|
Towers 1 & 2 Overhead Rough and Tenting. Call James before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|