FIR19-00960
| INSP-Final Inspection | 1/22/2020 | 1/24/2020 | 1/24/2020 8:02:49 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-04702
| FIRE-Final Inspection | 1/23/2020 | 1/24/2020 | 1/24/2020 8:02:18 AM | A | FAIL |
|
|
Provide access panels for in-duct smoke detectors. Sprinkler modifications are required in tenant space, multiple heads a less than 6 feet apart, multiple heads are blocked. Sprinkler head in female restroom has paint overspray on bulb as well as a painted upright next to main entry. Any and all modifications to fire sprinkler system requires a seperate permit before work can be started.
Brian Phone #: ###-####
|
FIR20-00008
| INSP-Final Inspection | 1/22/2020 | 1/24/2020 | 1/24/2020 8:00:12 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work complete.'
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|