Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00960 INSP-Final Inspection1/22/20201/24/20201/24/2020 8:02:49 AMACANC
Cancelled per conversation with point of contact, will be rescheduled for a later date.

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-04702 FIRE-Final Inspection1/23/20201/24/20201/24/2020 8:02:18 AMAFAIL
Provide access panels for in-duct smoke detectors. Sprinkler modifications are required in tenant space, multiple heads a less than 6 feet apart, multiple heads are blocked. Sprinkler head in female restroom has paint overspray on bulb as well as a painted upright next to main entry. Any and all modifications to fire sprinkler system requires a seperate permit before work can be started.

Brian Phone #: ###-####
FIR20-00008 INSP-Final Inspection1/22/20201/24/20201/24/2020 8:00:12 AMAPASS
Final fire alarm inspection for scope of work complete.'

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball