FIR04-00656
| INSP-Sprinkler Rough-in/Hydro | 1/24/2005 | 1/25/2005 | 1/25/2005 12:00:00 AM | P | CANC |
|
|
Cancelled per message left by Scott 1/25/2005 3:49:59 PM
|
FIR04-00666
| INSP-Sprinkler Rough-in | 1/24/2005 | 1/25/2005 | 1/25/2005 12:00:00 AM | P | PART |
|
|
The sprinkler piping in the east wing is ok to cover. Brian with Debest will verify that the electrician does not disturb the tenting prior to cover. Sprinkler piping rough-in in the west wing is ok. Needs tenting inspection before cover. 1/25/2005 3:33:55 PM
|
FIR04-00813
| INSP-Final Inspection | 1/24/2005 | 1/25/2005 | 1/25/2005 12:00:00 AM | P | FAIL |
|
|
Provide immediate shutdown for the hvac units. Provide the correct remote annunciator for the duct smoke detectors. Provide verification that the duct system over the lobby area has duct detector or that it is not required. 1/25/2005 3:35:44 PM
|
BLD04-02658
| FIRE-Final Inspection | 1/25/2005 | 1/25/2005 | 1/25/2005 12:00:00 AM | P | FAIL |
|
|
Repair emergency light in room 106 and final fire alarm system. 1/25/2005 3:36:23 PM
|
FIR05-00034
| INSP-Final Inspection | 1/25/2005 | 1/25/2005 | 1/25/2005 12:00:00 AM | P | FAIL |
|
|
Sprinkler work at the draftstop near at the south end of the store has not been done. Some deficiencies have been corrected that have not been shown on the plans. This includes four heads under a duct and a single upright under the old hood. Verify with Bill Alexander if resubmittal is required of just field verification. The tamper switch that is shown on the sprinkler plans has wire already run to the facp but no permit. 1/25/2005 3:10:26 PM
|
FIR04-00251
| INSP-Final Inspection | 1/25/2005 | 1/25/2005 | 1/25/2005 12:00:00 AM | P | FAIL |
|
|
General contractor is going to provide verification that the anti-freeze loop has indeed been inspected by Grinnell. Some of the pendant heads need the dry wall mud removed before final. 1/25/2005 12:24:05 PM
|
MIS04-00292
| FIR-Conference | 1/25/2005 | 1/25/2005 | 1/25/2005 12:00:00 AM | P | DONE |
|
|
The tamper switch that is shown on the sprinkler plans has wire already run to the facp but no permit. The store manager did not know who ran the wire. I told him that it required permits and would be required prior to signing a final for the store. I notified Mary about the alarm work.
|