Inspections for the day of: Wednesday, January 25, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03040 ELE-Aging Inspection1/25/20061/25/20061/27/2006 12:25:17 PM FAIL
nr cor. not made
ELE05-03913 ELE-Aging Inspection1/25/20061/25/20061/27/2006 8:44:40 AM PASS
ELE06-00183 Conference1/24/20061/25/20061/25/2006 4:42:20 PMADONE
talked wiyh owner he will have alloway make corrections on p/s done by prior owner on expired permit in 1999
ELE05-04023 Electrical Rough-In1/25/20061/25/20061/25/2006 4:20:42 PMPPART
Scheduled by a contractor via Hello! on 1/25/2006 at 10:19:37 AM. Contact: ###-####. ceilings ok
ELE06-00242 Permanent Service1/25/20061/25/20061/25/2006 3:41:31 PMPNH
Scheduled by a contractor via Hello! on 1/25/2006 at 6:52:33 AM. Contact: ###-####. notice posted called left message
ELE06-00291 Permanent Service1/25/20061/25/20061/25/2006 2:27:13 PMPCANC
Chuck ###-####
ELE06-00291 Permanent Service1/25/20061/25/20061/25/2006 2:26:28 PMPPASS
chuck ###-#### p/s u/g for meter ok
ELE05-04124 Final1/25/20061/25/20061/25/2006 1:58:21 PMPPASS
Scheduled by a contractor via Hello! on 1/25/2006 at 8:01:22 AM. Contact: ###-####. ok
ELE06-00235 Permanent Service1/25/20061/25/20061/25/2006 1:36:14 PMPFAIL
Internet Inspection Request from: Rowdy Monroe r/i & p/s failed cor. posted to both high and low voltage contractors called 250.148 terminate all equip grds together 2 gang box kit.,300.4 nail plates 11/4" for both high and low voltage,220.40 calc and provide p/s of required size for load, low voltage needs conn. for ent at cabinet
ELE06-00251 Rough-In Permanent Service1/24/20061/25/20061/25/2006 10:19:15 AMAPASS
charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis
r/i ok p/s u/g new ok
ELE05-04047 Final1/24/20061/25/20061/25/2006 9:48:56 AMAFAIL
Scheduled by a contractor via Hello! on 1/24/2006 at 1:05:06 PM. Contact: ###-####. fee due and new correction notice posted called left massage violations not corrected new one created 200.6 shall not ID #6 or smaller neutral green identified as white,
ELE06-00003 Final1/24/20061/25/20061/25/2006 9:10:23 AMAPASS
added arch fault for bedroom; Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ELE06-00026 Electrical Rough-In1/24/20061/25/20061/25/2006 8:23:57 AMAPART
ANY QUESTIONS PLEASE GIVE STEVE NUXOLL A CALL.; Phone #: ###-####
r/i all areas except grid ceiling
ELE05-04666 Conference1/24/20061/25/20061/24/2006 3:58:09 PMACANC
the address 7301 W Emerald Dr. Harmond office\\call ###-#### H P ///cancelled per H.P. 1/24/06 LEG Inspection cancelled from web by: Letitia Mesa