BLD05-02834
| FIRE-Final Inspection | 1/25/2006 | 1/25/2006 | 1/26/2006 2:44:35 PM | P | FAIL |
|
|
Repair and test all exit signs and emergency lights. Provide emergency lighting in the corridor in front of the new "Interview Room 102" and in the main lobby. Remove manual flush bolts from the doors into "Interview Room 102" and into the lobby. They are not allowed per IFC 1008.1.8.4 Automatic flush bolts are allowed. Provide lever hardware or crashbar on the north office area exterior exit door.
|
BLD05-02634
| FIRE-Final Inspection | 1/25/2006 | 1/25/2006 | 1/25/2006 3:38:25 PM | P | PART |
|
|
Life safety passed in the phase one area and is ok to occupy.
|
FIR05-00791
| INSP-Final Inspection | 1/25/2006 | 1/25/2006 | 1/25/2006 3:35:41 PM | P | PART |
|
|
Sprinklers are passed in the phase one area.
|
FIR05-00860
| INSP-Final Inspection | 1/24/2006 | 1/25/2006 | 1/25/2006 3:33:05 PM | A | PART |
|
|
Phase one area complete and ok to occupy. Need to test NAC panel and EOL when phase two is done. Provide sync'ing of the strobes in corridor (exit path from the remodeled space).
|
FIR06-00042
| INSP-Final Inspection | 1/24/2006 | 1/25/2006 | 1/25/2006 2:27:54 PM | P | CANC |
|
|
Appliances are missing. No inspection performed.
|
BLD05-03051
| FIRE-Final Inspection | 1/24/2006 | 1/25/2006 | 1/25/2006 2:27:11 PM | P | CANC |
|
|
Per owner the project is not ready for inspection
|
FIR06-00026
| INSP-Sprinkler Rough-in | 1/24/2006 | 1/25/2006 | 1/25/2006 11:56:20 AM | A | PASS |
|
|
Underground piping is ok to cover
|
FIR05-00876
| INSP-Sprinkler Rough-in | 1/24/2006 | 1/25/2006 | 1/25/2006 10:55:32 AM | A | FAIL |
|
|
Insulation backing is still laying on some of the heads in the east wing and the dry system piping in the second floor area has been covered without re-inspection. Backing needs fixed and the second floor backing removed so the piping can be inspected. "Do Not Cover" sticker was placed at the door.
|
BLD05-00988
| FIRE-Final Inspection | 1/19/2006 | 1/25/2006 | 1/25/2006 10:08:01 AM | A | PASS |
|
|
life safety finaled
|
FIR05-00215
| INSP-Final Inspection | 1/20/2006 | 1/25/2006 | 1/25/2006 10:07:12 AM | A | PASS |
|
|
permit finaled
|
FIR05-00780
| INSP-Alarm Testing | 1/23/2006 | 1/25/2006 | 1/25/2006 10:06:23 AM | A | PASS |
|
|
permit finaled
|
FIR05-00214
| INSP-Alarm Testing | 1/19/2006 | 1/25/2006 | 1/25/2006 10:05:54 AM | A | PASS |
|
|
permit finaled
|