Inspections for the day of: Thursday, January 25, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03985 ELE-Aging Inspection1/25/20071/25/20072/2/2007 9:20:36 AM DONE
see final
ELE06-03988 ELE-Aging Inspection1/25/20071/25/20071/26/2007 9:56:08 AM DONE
see final
ELE07-00114 Permanent Service1/23/20071/25/20071/25/2007 4:10:14 PMPFAIL
replacing bad panel - need insp. to have Idaho Power to turn power back on. For questions pls call Ryan w/doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### met contr, job not ready, talked about criteria for bringing service up to code, inside panel not mounted, nm cable from old panel not installed
ELE05-03825 Final1/25/20071/25/20071/25/2007 3:39:31 PMPPASS
cody; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
ELE07-00254 Electrical Rough-In1/25/20071/25/20071/25/2007 2:47:27 PMPPASS
****this is at 2809 1/2 W Agate St. Tennant is Danielle, she will be home. Phone #: ###-#### ri ok, see final
ELE07-00254 Final1/25/20071/25/20071/25/2007 2:47:01 PMPPASS
****this is at 2809 1/2 W Agate St. Tennant is Danielle, she will be home. Phone #: ###-#### ok to final
ELE06-04518 Permanent Service1/25/20071/25/20071/25/2007 1:45:33 PMPPASS
Please ask for Steve Berry if there is any problems. Thank you Phone #: ###-#### called contr about guy kit, protect gec, p/s o/h rec ok, 1 meter
ELE06-04468 Permanent Service1/25/20071/25/20071/25/2007 1:44:01 PMPPASS
If there are any problems please call Steve Berry. Thank you Phone #: ###-#### called contr to provide guy kit and protect gec, p/s o/h rec ok 1 meter
ELE06-03829 Final1/24/20071/25/20071/25/2007 12:02:44 PMAFAIL
Requesting a final inspection. Phone #: ###-#### called, left corr notice, nec 605.7 multiwire branch ckts to partitions shall simultaneously disconnect at panelboard where ckt originates, 330.30(B) mc cable shall be strapped within 12" of panel, 408.4 circuit directory shall be permanent, clear, and concise, 110.3(A) equipment shall be listed and labelled, BCC no violations shall be retained, BCC 4-05-33(A)(B) all equipment shall be listed and labelled by a nationally recognized testing laboratory
ELE07-00262 Electrical Rough-In1/24/20071/25/20071/25/2007 10:38:34 AMAPASS
dave; Phone #: ###-#### Internet Inspection Request from: Victoria Beall u/g ok to cover
ELE06-03194 Final1/25/20071/25/20071/25/2007 9:45:55 AMAPASS
Scheduled by a contractor via Hello! on 1/25/2007 at 6:43:38 AM. Contact: ###-####. told owner to strap flex out of panel, ok to final
ELE06-04404 Electrical Rough-In1/24/20071/25/20071/25/2007 9:05:17 AMAPART
Scheduled by a contractor via Hello! on 1/24/2007 at 2:15:50 PM. Contact: ###-####. ok to cover dropped clg only
ELE07-00256 Temporary Service1/24/20071/25/20071/25/2007 9:04:02 AMAPASS
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g n ok, talked to contr, will re-permit for perm power