Inspections for the day of: Thursday, January 25, 2007.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00399 FIR-Aging Inspection1/25/20071/25/20071/30/2007 9:29:45 AM DEFR
MIS06-00033 MIS-Aging Inspection1/25/20071/25/20071/30/2007 9:29:35 AM DEFR
MIS05-00071 MIS-Aging Inspection1/25/20071/25/20071/30/2007 9:29:23 AM DEFR
BLD05-02051 FIRE-Final Inspection1/25/20071/25/20071/26/2007 4:16:34 PMPPASS
Fire life safety inspection passed, correction notice issues are complete.
BLD05-02962 FIRE-Final Inspection1/25/20071/25/20071/26/2007 4:15:50 PMPPASS
Items on previous c/n are finished, fire life safety passed.
BLD05-02052 FIRE-Final Inspection1/25/20071/25/20071/26/2007 4:15:16 PMPPASS
C/N items verified for completion, fire life safety passed.
FIR07-00042 INSP-Final Inspection1/25/20071/25/20071/26/2007 10:08:10 AMPPASS
1st floor tenant fire alarm permit work passed inspection.
FIR06-00715 INSP-Alarm Testing1/25/20071/25/20071/26/2007 9:50:15 AMPDEFR
Inspection scheduled for 1/26 as agreed.
BLD06-01896 FIRE-Final Inspection1/24/20071/25/20071/26/2007 8:25:35 AMPPASS
Fire life safety inspection passed.
FIR06-00651 INSP-Final Inspection1/24/20071/25/20071/26/2007 8:17:39 AMPFAIL
Per field inspection completed by M. Timmerman defficiencies noted and some revisions will be required.
FIR06-00699 INSP-Final Inspection1/24/20071/25/20071/26/2007 8:14:25 AMAPASS
Per field inspection completed by M. Timmerman, the hood suppression system operated correctly under test conditions, inspection passed, permit finaled.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro1/23/20071/25/20071/26/2007 8:11:48 AMAPART
Completed fire pump field acceptance test including pump curve, flow testing, controller operation, engine drive, and jockey pump. Noted some items in need of revision including removal of the ball valves in the pressure sensing lines (NFPA 20 12.5.2.1.6 B3), the exhaust pipe shall be covered or insulated per 11.5.3.3, repair the leak in the 1/2" cooling line at the engine, provide missing stop button at the controller. Also completed acceptable standpipe flow testing via fire pump and FD pumper vehicle.
BLD06-03222 FIRE-Final Inspection1/25/20071/25/20071/25/2007 5:43:36 PMAPASS
Fire life safety passed final inspection.
FIR06-00999 INSP-Final Inspection1/24/20071/25/20071/25/2007 1:14:01 PMPCANC
Inspection canceled per phone call from the contractor.
FIR06-00946 INSP-Final Inspection1/24/20071/25/20071/25/2007 1:13:12 PMPCANC
Cancel inspection per phone call from contractor.
FIR06-00816 INSP-Final Inspection1/24/20071/25/20071/25/2007 1:12:19 PMAPASS
Fire alarm work is satisfactory, permit finaled.
BLD06-02877 FIRE-Final Inspection1/24/20071/25/20071/25/2007 11:51:50 AMAPASS
Life safety inspection passed.
BLD06-01413 FIRE-Final Inspection1/24/20071/25/20071/25/2007 11:38:04 AMAFAIL
Final pending the project related fire alarm permit work.
FIR06-00985 INSP-Sprinkler Rough-in/Hydro1/24/20071/25/20071/25/2007 10:55:04 AMAPART
UG fire supply line is approved for bury.
FIR06-00986 INSP-Sprinkler Rough-in/Hydro1/24/20071/25/20071/25/2007 10:54:20 AMAPART
UG supply line is approved for cover.
FIR06-00706 INSP-Final Inspection1/24/20071/25/20071/25/2007 10:53:41 AMAPASS
Fire sprinkler permit passed final inspection.